1. INSTALLATION
INST
ALLER
CONDENSATE NEUTRALIZER KIT
The condensate neutralization system neutralizes
the condensate created by the products of
combustion.
Acid condensate, introduced into the neutralization
box, follows a two-step set course. First phase:
nitrates and sulphates filtration through active
carbons contained in the first part of the carbon
site pipe. In the second phase the pH rises.
The acidity of the condensate can be controlled
through the use of appropriate tools for the
determination of Ph, such as the litmus paper.
Neutralized condensate can then be routed to the
drainage system.
Maintenance
The pH value of the condensate after the neutralizer
must be in between
<5,5 – 9,5>
.
Every six months, you need to determine the pH of
the condensate treated in the neutralizer. Litmus
paper or a digital instrument can be used to
measure the pH level.
Neutral point is on the 6,8-7 value; in case of lower
value the condensate is acid, in case of a higher
value it is basic.
If necesssary, replace the active carbon and the
reagent granulate.