1. INSTALLATION
INST
ALLER
1.1.21. TABLE 1: ALLOWABLE VENT LENGTHS
NOTE: In Canada, exhaust vent must be approved to ULC S636 standard.
Each 2”/ 3”/ 4”/60mm/80mm 45° elbow equates to 2.5 linear feet to vent pipe.
Each 2”/ 3”/ 4”/60mm/80mm 90° short radius elbow equates to 7.5 linear feet to vent pipe.
Each 2”/ 3”/ 4”/60mm/80mm 90° long radius elbow equates to 5 linear feet to vent pipe.
Each 125mm-80mm 45° elbow equates to 5 linear feet to vent pipe.
Each 125mm-80mm 90° short radius elbow equates to 16.4 linear feet to vent pipe.
Each 125mm-80mm 90° long radius elbow equates to 12 linear feet to vent pipe.
The total maximum equivalent vent pipe distance cannot exceed the maximum length listed for horizontal
and vertical venting distance.
The maximum lengths are not including elbows unless otherwise stated.
Exceeding the maximum venting distances will cause the appliance to malfunction or cause an unsafe
condition.
Vent
Cofiguration
Pipe Size
Minimum
Lenght Vertical
and Horizontal
per Vent Run
Max Equivalent
lenght Vertical and
Horizontal per vent
run
Gas Type
Exhaust Vent
Intake Vent
Horizontal
Co-axial vent S636
Polypropylene
80mm –
60mm
1 ft (0.3 m) +
elbow
3.28 ft (1 m) + elbow Natural or
Propane
Polypropylene
Polypropylene
Horizontal
Co-axial vent S636
Polypropylene
125mm –
80mm
3.3 ft (1 m) +
elbow
16.4 ft (5 m) + elbow Natural or
Propane
Polypropylene
Polypropylene
Horizontal/
Vertical Co-linear
Vent** (2 Separate
pipes)
2" /
60mm
3.3 ft (1 m)
41 ft (12.5 m)*
Natural or
Propane
PVC, CPVC,
Polypropylene
PVC, CPVC, Poly-
propylene, ABS
Horizontal/
Vertical Co-linear
Vent** (2 Separate
pipes)
3" / 80
mm
3.3 ft (1 m)
85 ft (26 m)
Natural or
Propane
PVC, CPVC,
Polypropylene
PVC, CPVC, Poly-
propylene, ABS
Horizontal/
Vertical Co-linear
Vent** (2 Separate
pipes)
4" /
100 mm
3.3 ft (1 m)
150 ft (46 m)
Natural or
Propane
PVC, CPVC,
Polypropylene
PVC, CPVC, Poly-
propylene, ABS
Horizontal/
Vertical Forced Draft
2" /
60mm
1.6 ft (0.5 m)
41 ft (12.5 m)*
Natural or
Propane
PVC, CPVC,
Polypropylene
PVC, CPVC, Poly-
propylene, ABS
Horizontal/
Vertical Single Vent
3" /
80 mm
1.6 ft (0.5 m)
65 ft (20 m)
Natural or
Propane
PVC, CPVC,
Polypropylene
PVC, CPVC, Poly-
propylene, ABS
Horizontal/
Vertical Single Vent
4" /
100 mm
1.6 ft (0.5 m)
100 ft (30 m)
Natural or
Propane
PVC, CPVC,
Polypropylene
PVC, CPVC, Poly-
propylene, ABS
INSTALLATION
Gas Type
Minimum Heating Frequency
Maximum Heating Frequency
(Hz)
(Hz)
Gas A (Natural)
46
255 (270*)
Gas E (Propane)
47
251 (270*)
* The frequency must be change to a value of 270 Hz only with 2” diameter pipe that has a total vent run
of above 18 ft (5.5 m).
** Vent run consists of allowable vent length for exhaust pipe and an additional allowable vent length
for combustible air.
Содержание SFK 55
Страница 6: ......
Страница 32: ......
Страница 61: ...61 SFK 55 RAD ING Manual 1512 2_CSA_TTS 3 USE USER ...
Страница 62: ...62 SFK 55 RAD ING Manual 1512 2_CSA_TTS 3 USE USER ...
Страница 63: ...63 SFK 55 RAD ING Manual 1512 2_CSA_TTS 3 USE USER ...
Страница 64: ...64 SFK 55 RAD ING Manual 1512 2_CSA_TTS 3 USE USER ...
Страница 73: ......
Страница 74: ......
Страница 75: ......