2.2.15. FAULT SIGNALLING CODES
To view the last 5 fault signalling codes chronologically, starting with the most recent one, activate the
‘OFF’ mode by pressing the FUNCTION ‘
’ key and hold the key INFO ‘
’ for 5 seconds. Use keys ‘
’ and ‘
’ of the symbol recirculation
to scroll through the list of saved faults. To reset the fault
history press the RESET ‘
’ key. To exit display mode press the INFO ‘
’ key.
CODE
FAULT
POSSIBLE CAUSE
SOLUTION
RESET
E01
FLAME FAILURE
AIR PRESSURE
SWITCH
NO FLAME LIGHT UP
MANUAL RESET
(PRESS THE RESET
‘
’ KEY).
NO GAS PRESSURE;
CHECK THE GAS SUPPLY NETWORK;
MASS OR BROKEN START-
UP ELECTRODE;
REPLACE IT;
GAS VALVE NOT OPENING;
REPLACE IT;
SLOW LIGHT UP TOO LOW
ADJUSTMENT;
ADJUST MINIMUM OR SLOW LIGHT UP;
VALVE INFEED PRESSURE
TOO HIGH (ONLY FOR GPL
WATER HEATERS).
CHECK THE MAXIMUM ADJUSTMENT
PRESSURE
WITH FLAME LIGHT UP
NEUTRAL AND PHASE
INVERTED POWER SUPPLY;
PROPERLY CONNECT THE POWER
SUPPLY;
IONIZATION ELECTRODE
BROKEN;
REPLACE IT;
IONIZATION ELECTRODE
CABLE DISCONNECTED.
CHECK THE WIRING.
ELECTRICAL CURRENT
PHASE-PHASE
SWITCH OUT OF ORDER,
EXHAUST VENT OR AIR
INLET PIPE OBSTRUCTED
IF THE TENSION MEASURES BETWEEN
NEUTRAL AND GROUND IS ALMOST
EQUAL TO THE ONE MEASURED
BETWEEN PHASE AND GROUND, YOU
HAVE TO INSTALL A PHASE-PHASE
TRANSFORMER KIT (COD. 88021LA)
REPLACE PART ,
CHECK EXHAUST VENT OR AIR INLET
PIPE
MAINTENANCE
Содержание SFK 55
Страница 6: ......
Страница 32: ......
Страница 61: ...61 SFK 55 RAD ING Manual 1512 2_CSA_TTS 3 USE USER ...
Страница 62: ...62 SFK 55 RAD ING Manual 1512 2_CSA_TTS 3 USE USER ...
Страница 63: ...63 SFK 55 RAD ING Manual 1512 2_CSA_TTS 3 USE USER ...
Страница 64: ...64 SFK 55 RAD ING Manual 1512 2_CSA_TTS 3 USE USER ...
Страница 73: ......
Страница 74: ......
Страница 75: ......