4. Configuration and operation
To operate the data logger, either a wired (Ethernet) or wireless (Wi-Fi, 3G/4G/LTE) connection is
required. The data logger is accessed by the IP address of the device with a proper connection port
indicated. To operate in this mode, you can use any device (PC, laptop, tablet PC or mobile phone) with
the latest versions of Internet browsers such as Chrome, Safari, Internet Explorer and so on.
Operation and configuration of the device is also possible through the virtual LAN driver (RNDIS)
via the USB interface. In this case, a PC-compatible computer or Laptop running Windows, Linux or
MacOS is required to operate.
The device terminal can also be accessed through the virtual serial port driver via the USB interface.
Software for the NDAS-N data logger and the NDAS-RT multifunction module is identical.
The functions and capabilities described in this chapter for NDAS-RT also refer to the data
logger.
At an initial connection, the data logger receives an IP address via DHCP from the router. Further
access to the device is carried out by typing in the address bar its IP address with indicating port 8000.
For example, http://192.168.0.163:8000 where 192.168.0.163 is the address and 8000 is the port number.
The automatically assigned IP address can be changed to a fixed one in the settings of the network
equipment (Router).
If it is not possible to find out the IP address assigned to the device, use the following
algorithm: connect the device simultaneously to the Ethernet network (via wire or Wi-Fi) and
to the PC via the micro-USB interface, make sure that your PC has the Ethernet virtual
network driver correctly installed. Go to the web interface of the device at 192.168.7.2: 8000
– the IP address of the Ethernet connection will be displayed on the main page in the Networks
– Ethernet – details or Networks– Wi-Fi – details sections.
When you access the data logger’s web interface, a login and password are requested. At the default
settings, the data logger uses the ‘
ndasrt’
login and the ‘
ndasrt’
password. Further on, it is recommended
changing the password in the settings.
After entering the login and password, you go to the System status page.