Chapter 3: FRU Removal and Replacement Procedures
Replacing Node Power Supplies
Quantum DXi6900 G2 Field Service Manual
79
l
ESD grounding wrist strap (included in the replacement kit)
Figure 39:
DXi6900 G2 Node Power Supply
Illustration
Description
Replacement power supply for DXi6900 G2 Node (750 watt)
Replacing a Node Power Supply
This section describes how to remove and replace a power supply in the DXi6900 G2 Node. If a power
supply fails, you will be notified by a service ticket in the remote management console.
Caution:
Use appropriate ESD precautions, including the use of a grounding strap, when performing
this procedure.
Removing and replacing a power supply in the Node includes the following steps:
l
Identifying a Failed Power Supply in the Node below
l
Removing a Failed Power Supply from the Node on the next page
l
Installing a Replacement Power Supply in the Node on page 81
Identifying a Failed Power Supply in the Node
The DXi6900 G2 Node contains two hot-swappable power supplies (see
).
Figure 40:
DXi6900 G2 Node Power Supplies
1
1
1. Power supplies
Use the indicator LEDs on the power supply to identify the failed power supply (see
).