10.3 Calibrating an Expansion Pod Equipped Library
10-10
501801 Rev. 07-01-19
10.3.1 The Calibration Procedure
1.
Shut down the XLS Tape Library and switch the power switch to off.
2.
Open the LRM door.
3.
Expansion pod columns are designated A as the front column, the column closest
to the front of the library, and B as the rear column. See
4.
Make sure the XLS tape library has firmware Version 2.01.F001 PODS
SUPPORT or higher installed..
Figure 10-9
Pod calibration cartridge with the CAL label attached
Figure 10-10
Column A and B locations in an expansion pod
CAL Label
Column A
Column B