8. Click [Next].
The
Output Channel Calibration
window displays again.
9. Adjust the slide bar control until the ammeter displays the correct upper calibration value
for the new current loop output range.
Current Loop
Output Range
Upper
Calibration Value
4 - 20 mA
20.00 mA
0 - 5 mA
5.00 mA
0 - 10 mA
10.00 mA
0 - 20 mA
20.00 mA
10. Click [Finish].
11. Repeat the process for the remaining current output loops. When you are finished,
immediately exit from the Calibrator tool.
The current loops are now be calibrated for the new values.
Output Channel Calibration