Current input
module
Allows you to select the input module number that measures the motor
current from the fans or pumps that start when the bank actuating relay is
actuated.
Important:
This variable must be set correctly before using the
Cooling Monitor Initialization feature
. If the 509ITM-200
does not have at least one current input module installed,
the Cooling Monitor Feature will not function.
Alarm relay
Allows you to select a relay number to actuate if any of the selected
parameters exceed threshold values.
Important:
This alarm relay is configured in this window and not in the
. If the selected relay was
assigned earlier to function for a different control signal, it
will no longer operate for that function. Conversely, if you
open the
Output Relay Setup
window and reconfigure the
alarm relay that you selected here to be a matrix-controlled
relay, the relay will no longer operate as a cooling system
alarm relay.
Cooling bank
Allows you to enable or disable the Cooling Monitor.
Note:
If you disable all the cooling banks, the Cooling Monitor will not be
active, and none of the values will be displayed in the MENU
Mode on the front panel of the 509ITM.
Relay
operation
Allows you to set the actuation of the relay to either
Failsafe
or
Non-
failsafe
Test lock out
Allows you to set this function to:
•
On
- The alarm relay does not change states when the
TEST
button
on the front panel of the 509ITM is pressed.
•
Off
- The alarm relay changes states when the
TEST
button on the
front panel of the 509ITM is pressed.
Actuation
delay
Allows you to enter the delay time, in minutes, of the actuation of the
alarm relay after any of the active parameters exceed their setpoint.
Note:
This function does not apply to these sections of the
•
Running Bank Current
•
Starting Motor Current Value
(peak currents)
•
Number of Actuations
•
Run Time
Содержание 509ITM Series
Страница 26: ...26 www qualitrolcorp com Current Input Wiring...
Страница 55: ...55 www qualitrolcorp com 3 Continue with the setup procedure...
Страница 101: ...101 www qualitrolcorp com...
Страница 144: ...144 www qualitrolcorp com The following window will appear...
Страница 167: ...167 www qualitrolcorp com The Customer Setup window displays 4 Click Load Tap Changer...
Страница 178: ...178 www qualitrolcorp com Appendix...
Страница 179: ......
Страница 180: ......
Страница 181: ......