www.qualitrolcorp.com
Establishing Communications with the 509ITM
window, select, set, or observe the following items as
required:
Address
Each 509ITM has an assigned address that allows multiple 509ITMs to
be used with a common communication link. The factory default
configuration has an address of 00. (For one on one communications
leave as the factory default). Select the correct address from the pull-
down menu.
Baud Rate
The baud rate on your PC must be the same as that on the 509ITM
monitor with which you are communicating. The range is 1,200 - 38,400
for the RS232 port and 1200
– 230,400 for the USB port. The default is
19,200. Select the correct baud rate from the pull-down menu. If the
baud rate is unknown, it is possible to view it on the LCD display of the
509ITM. Enter the MENU Mode and go to the Change Settings column
(see the
COM
Allows you to select the serial communications port on the PC. The
default is COM1. Select the communication port that the serial port is
connected to on your PC.
Off line
You can run the software offline without being connected to the
509ITM.
1. With no communications to the 509ITM established, click the
Off
line
check box.
2. Click on the Connect button.
3. Select the 509ITM icon and hit the Connect button.
4. Type
demo
into the
Password
field of either the
Setup - Customer
or
Setup - Factory
application section.
The
Setup
window opens and displays the available features. This
feature is useful during training or to learn how the product functions
when there is no 509ITM available.
Important:
Changes made in the Demo mode are not permanent.
These modifications cannot be saved or downloaded into
a device.
Connect Button
Click to start or end communications with a 509ITM.
TX and RX
Displays transmission activity.
Note:
Short transmissions will often occur too fast to be viewed by the
operator.
IP Address
The ITM Manager can be used to communicate remotely over an
Ethernet connection to a 509ITM by entering the IP Address of that
509ITM in this box. Note: The 509ITM must have Ethernet capability
and be available on the network connection.
Port
To communicate to a 509ITM over an Ethernet connection the port of
the 509ITM must be entered in this window box.
Содержание 509ITM Series
Страница 26: ...26 www qualitrolcorp com Current Input Wiring...
Страница 55: ...55 www qualitrolcorp com 3 Continue with the setup procedure...
Страница 101: ...101 www qualitrolcorp com...
Страница 144: ...144 www qualitrolcorp com The following window will appear...
Страница 167: ...167 www qualitrolcorp com The Customer Setup window displays 4 Click Load Tap Changer...
Страница 178: ...178 www qualitrolcorp com Appendix...
Страница 179: ......
Страница 180: ......
Страница 181: ......