77
www.qualitrolcorp.com
Oil Time
Constant
(4 fields)
Allows you to set the time constant for the temperature rise of this
winding. The time constant is defined as the time it takes the winding
temperature to reach 63.2% of its final value for a given current input.
Note:
It takes approximately five time constants to elapse for the
temperature to reach full value for a given load. If the oil time
constant is not provided, the IEC 354 Loading Guide for Oil-
Immersed Power Transformers recommends:
For Distribution Transformers:
•
All cooling types: 180 minutes
For Medium and Large Transformers:
•
ON (natural convection): 150 minutes
•
OF (forced oil): 90 minutes
•
OD (directed forced oil): 90 minutes
Содержание 509ITM Series
Страница 26: ...26 www qualitrolcorp com Current Input Wiring...
Страница 55: ...55 www qualitrolcorp com 3 Continue with the setup procedure...
Страница 101: ...101 www qualitrolcorp com...
Страница 144: ...144 www qualitrolcorp com The following window will appear...
Страница 167: ...167 www qualitrolcorp com The Customer Setup window displays 4 Click Load Tap Changer...
Страница 178: ...178 www qualitrolcorp com Appendix...
Страница 179: ......
Страница 180: ......
Страница 181: ......