99
www.qualitrolcorp.com
The
Critical Forecast
section includes the fields described below.
Critical
Temperature
(3 Range
fields)
Allows you to enter three temperature values for monitoring the time it
takes for the winding temperature to reach the present load conditions.
Time to
Critical
Temperature
(3 Range
fields)
Displays the time calculated for the winding temperature to reach the
critical setpoint values, given the present loading, oil/winding
temperatures, and ambient conditions.
If the number displayed is 0.00 hours, the winding temperature has
already reached the critical point. If 99.9 hours are displayed, the winding
temperature will never reach the critical point, given these loading
conditions.