Type
Indicates the type of signaling hardware used for the Auxiliary Port. This
field is for informational purposes only.
DGA
Checking the install boxes will enable communications to the DGA
sensor(s). The 509ITM can support up to three hydrogen sensors. DGA
1 will have an address of 16, DGA 2 will have an address of 17, DGA will
have an address of 18. Make sure the sensor installed selection
matches the address of the sensor being used.
Protocol
All digital sensors connected to the Auxiliary Port use the Modbus
protocol.
Address
Slave
Not used for the Hot Spot Module, DGA sensor or Expansion Module
communications.
Baud Rate
The Baud Rate for all digital communications is 9600.
Number of
Data Bits
The Data Bits for digital communications should be set to 1.
Optical Hot
Spot Module
X installed
If this box is checked then the software is capable of communicating with
a Hot Spot Module.
Enabled /
Disabled
Selecting these radio buttons will disable or enable the Hot Spot Module.
X Fiber
Channel
The radio button selected shows how many fibers are active on the Hot
Spot Module
Address
For the Optical Hot Spot Module
1 this should be set to ‘1’, for the Optical
Hot Spot Module 2 this should be set to ‘2’. The addresses on the Hot
Spot Modules should match these settings. Two Hot Spot Modules with
the same address will not function.
Содержание 509ITM Series
Страница 26: ...26 www qualitrolcorp com Current Input Wiring...
Страница 55: ...55 www qualitrolcorp com 3 Continue with the setup procedure...
Страница 101: ...101 www qualitrolcorp com...
Страница 144: ...144 www qualitrolcorp com The following window will appear...
Страница 167: ...167 www qualitrolcorp com The Customer Setup window displays 4 Click Load Tap Changer...
Страница 178: ...178 www qualitrolcorp com Appendix...
Страница 179: ......
Страница 180: ......
Страница 181: ......