Loop Parameters
includes the fields described below.
Output Loop
Displays the number of the analog current loop that is to be configured.
Loop function
Allows you to enable or disable the output loop operation.
Loop type
Allows you to select between current loop ranges of 0 - 1 mA and 4 - 20
mA.
Note:
If requested at the time the monitor is ordered, this field can be
made to select between current loop ranges of 0 - 1 mA and 0 -
10 mA.
Custom Range
allows you to select the value range for the
current loop output.
Example:
An RTD measures temperatures from -40 - 120° C. You select an output of 4 - 20
mA and a custom range of 0 - 100. For temperature measurements of:
•
−
40 - 0° C, the current loop output will read 4 mA
•
0 - 100° C, the output will correspond directly to 4 - 20 mA
Any temperature measurement over 100° C will continue to read 20 mA.
The fields in this section of the
Output Loops Setup
window are described below.
Use Custom
Range
Allows you to activate the custom scaling of the analog outputs by
clicking to put a check mark in the check box.
Minimum
Allows you to enter a value that corresponds to 0 mA for a 0 - 1 mA
output, or 4 mA for a 4 - 20 mA output loop.
Maximum
Allows you to enter a value that corresponds to 1 mA for a 0 - 1 mA
output, or 20 mA for a 4 - 20 mA output loop.
Содержание 509ITM Series
Страница 26: ...26 www qualitrolcorp com Current Input Wiring...
Страница 55: ...55 www qualitrolcorp com 3 Continue with the setup procedure...
Страница 101: ...101 www qualitrolcorp com...
Страница 144: ...144 www qualitrolcorp com The following window will appear...
Страница 167: ...167 www qualitrolcorp com The Customer Setup window displays 4 Click Load Tap Changer...
Страница 178: ...178 www qualitrolcorp com Appendix...
Страница 179: ......
Страница 180: ......
Страница 181: ......