The
Calibrator - Signal Selection
window displays with the radio button for
Input 1
selected.
CAUTION:
Be extremely careful in the Calibrator tool. Changing calibration
values incorrectly might cause the 509ITM to malfunction.
4. Connect the ammeter (or multi-meter set to measure DC milliamps) to TB2 pins 1 and 2
with the positive probe on 1.
5. In the
Calibrator - Signal Selection
window, select the radio button for
Output 1
and click
[Calibrate].
The next two windows that appear are for calibrating the 0 - 1 mA section, which will
remain the same.