Status- and Fault Messages
Operating Status:
Fault-
Number
LED 1*
LED 2*
Meaning
40, 50
OFF
OFF
The inverter runs through the specified self-test before
connecting to the grid.
OR
Insufficient PV power available for feeding into the grid
(e.g. night operation)
10
ON
OFF
Feed-in mode, inverter connected to the grid.
20, 30
FLASHING
OFF
The inverter is limiting the feed-in power.
OR
The power supply company is limiting the feed-in
power actively.
160
FLASHING
ON
The inverter is limiting the feed-in power because the
inverter temperature is too high.
div.
OFF
ON
Inverter fault Use display text and chapter 9 Status
and fault handling
*
LED 1 = Infeed operation
LED 2 = Fault
Status and fault messages:
OID
Display text
Meaning
Remedial measure
1
---
10
Status: Feed-in mode
Inverter is connected to the
grid.
---
20
Status: Current limitation /
power limitation
Feed-in power limited by the
inverter. Cause: high radiation
or over- dimensioned generator
---
30
Status:
Ext. power reduction
Feed-in actively limited by the
power supply company or
inverter is reducing the power
due to overfrequency as per the
default characteristic P(f).
---
40
Status: Self-test
The inverter is running through
the specified self-test before
connecting to the grid.
---
50
Status:
DC-power too low
Insufficient generator output
power
his is a normal operating
condition with low radiation.
If this message occurs when
there is normal or high
radiation, check the
dimensioning of the PV
system or correct
interconnection of the
modules.
100
Update - Fault
The software update could not
be completed successfully
Repeat the process, contact
the Service Department of it
occurs again
110
Device Fault: Flash
Flash
Reading from or writing
onto the internal data memory
was not possible.
Contact the Service
Department
130
Device fault: Field bus
communication
Fault in external device
communication
With frequent occurrences:
Contact the Service
Department
140
Device fault: internal
communication
Fault in internal device
communication
With frequent occurrences:
Contact the Service
Department
150
Fan fault
A fan signals a fault
If applicable clean fan
carefully by blowing it out,
do not use any solvents. If
the problem persists:
Contact the Service
Department