4.13
Signal/control contact (RELAY)
The inverter has a potential-free signal contact (make contact). It is connected
via a 4- core M12 plug connector.
The inverter fault message is transmitted to the relay in the factory default
setting. Please refer to 7.2.10 Own consumption for an alternative use.
CAUTION
Please observe the maximum permissible current via the relay. See chapter 10.1
Technical data
4.13.1
Q
X
³10000-18000
Schematic
drawing:
Pin
configuration:
Relay Assignment:
Pin
Plug
Relay contakt
1
Output 1
Make contact 1 (NO, open in idle mode)
2
---
---
3
Output 2
Make contact 2 (COM)
4
---
---
Recommended cable cross sections
Without a plastic sleeve: 0.2 to 1.5 mm², with plastic sleeve: 0.2 to 0.75 mm²
Cable diameters: 4…8mm
Signal contact connection:
No.
Action
1
Connect the signal line of the relay control signal to the plug connector via the cable.