PULSAR MEASUREMENT
63
Configuration/Holding Registers (Parameters)
The first table presents the unit symbols and their corresponding
descriptions for the
Configuration Registers
(Parameters). The second table
shows the addresses, descriptions, and units of the
Configuration
Registers.
These registers are read/write (see Chapter 5 for details of each parameter),
and can be accessed using the Function Codes 3, 6 and 16.
Example:
You wish to know the current value for Empty Level. Search for register
address 105 with Function 3 and the information will then be displayed.
UNIT
DEFINITION
U_NO
None
U_MU
Measurement Unit
U_PC
Percentage
U_VU
Volumetric Unit
U_TP
Degree C
U_MN
Minutes
U_VEL
m/sec
U_MV
Millivolt
Application
32BIT
REGISTER
ADDRESS
2X 16BIT
REGISTER
ADDRESS
DESCRIPTION
UNIT
100
2052-2053
Mode
U_NO
101
2054-2055
Transducer
U_NO
102
2056-2057
Material
U_NO
104
2058-2059
Measurement Unit
U_NO
105
2060-2061
Empty level
U_MU
106
2062-2063
Span
U_MU
107
2064-2065
Near blanking
U_MU
108
2066-2067
Far blanking
U_PC