dBi-M
INSTRUCTION MANUAL
48
Modbus Poll Address
P133 Poll Address
This parameter sets the Modbus address for the dBi-M Intelligent
Transducer.
Default = 126
Alarm limits
The dBi-M series intelligent transducer stores an echo trace internally when
the Alarm condition is triggered. When requesting an echo trace the Alarm
trace will be displayed on the graph.
The dBi-M can be set up to capture an echo trace under certain alarm
conditions;
Alarm Trace
(activates within the setpoints set in (
P951
and
P952
) or
LOE Trace
.
P951 Low Limit
This parameter sets the low value (in
P104 measurement units
) for the
alarm setpoint.
P952 High Limit
This parameter sets the high value (in
P104 measurement units
) for the
alarm setpoint.
P953 Alarm Save Trace Mode
This parameter sets the frequency at which a trace is saved to the dBi-M
’s
internal memory in an alarm condition.
OPTION
DESCRIPTION
0 = Off (Default)
Trace mode is turned off.
1 = Once
When an alarm condition is activated, the dBi-M
will save the first trace in its internal memory.
2 = Repeatedly
When an alarm condition is activated, the dBi-M
will save the trace in its internal memory
overwriting the previous trace for the new one.