P21 Set Distance
Allows the user to determine which echo is to be displayed. On start-up, if
the unit displays an incorrect reading, then simply enter the distance from
the transducer to the required level and, if an echo is present at this point,
the Gate will establish itself around the chosen echo, DATEM will update in
front of the Gate and reference out any other unwanted echoes.
It should be noted that DATEM will reset to default values whilst performing
this function, and reform itself once it has selected an echo.
Enter the distance from the face of transducer to the target in
Measurement
Units
(
P104
).
P905 Peak Clearance
This parameter is used to set the height by which the DATEM trace will
“stand
-
off” from
the peak of unwanted echoes such as obstructions. Please
consult Pulsar Measurement for further information and assistance on
changing the value of this parameter.
P906 Side Clearance
This parameter is used to set the distance by which the DATEM trace will
“stand
-of
f” from around unwanted echoes such as obstructions. Please
consult Pulsar Measurement for further information and assistance on
changing the value of this parameter.
P70 DATEM Speed
This parameter is used to the speed in which the DATEM trace will react.
Please consult Pulsar Measurement for further information and assistance on
changing the value of this parameter.
OPTION
DESCRIPTION
0 = Slow (Default)
Datem updates to changes on an echo at a slow
rate.
1 = Medium
Datem updates to changes on an echo at a
medium rate.
2 = Fast
Datem updates to changes on an echo at a fast
rate.