CHAPTER 7 TROUBLESHOOTING
This section describes many common symptoms, with suggestions as to
what to do. If the issue persists, please contact your local Pulsar
Measurement Partner.
SYMPTOM
WHAT TO DO
Transducer not firing.
Check power supply to the transducer, and
any cable extensions.
Unable to connect to dBi-M PC
Ensure the dBi-M connections are correct,
the comport is set correctly. And
search/poll has been pressed. If issue
persists, try another comport for
connecting the interface cable.
Unable to view echo trace
Ensure that the transducer is connected
and has been polled. Press the Regular
Echo Off button.
dBi-M does not appear on Modbus
list
Ensure that the poll address is different to
the master and any other slave addresses
connected. By default, the dBi-M address
is set to 126. This can be changed in P133.
Incorrect reading being displayed
for current level.
Make a connection to dBi-M PC, measure
actual distance from transducer head to
surface of material. Use the function P21 in
common settings to set the distance that is
required to be measured.
Material level is consistently
incorrect by the same amount.
Check empty level, (P105), Span (P106) and
measurement offset (P851).
If you experience any other issues that are not mentioned in the above
troubleshooting guide, please contact your local Pulsar Measurement
Partner for further assistance.