Diagnostics and Troubleshooting
MVI56E-FLN ♦ ControlLogix Platform
User Manual
FA Control Network Ethernet Communication Module
Page 76 of 155
ProSoft Technology, Inc.
3.1.1 Own-Node Status information
The Own Node Status register (displayed on the Own Node Status menu)
contains the following information:
Own Status Byte
Bit
Message
Description
Value
0
Node address duplicate
(1=Error)
Indicates the management information on
node number conflicted to see whether any
node having the same node number as the
self node setting exists on the network or not.
0x0001
1
TW Error (1=Error)
Token watchdog time error flag indicates that
transmission processing fails to complete
within the token watchdog time set in the own
node
0x0002
2
Rx Wait Error (1=Error)
Indicates that no frame has been received at
network initialization, being a frame receive
waiting status.
0x0004
3
Initialization Error
(1=Error)
Indicates an error is found in an initial setting
or resetting parameter
0x0008
4
Reserved
0x0010
5
Reserved
0x0020
6
Reserved
0x0040
7
0x0080