MVI56E-FLN ♦ ControlLogix Platform
Configuring the MVI56E-FLN Module
FA Control Network Ethernet Communication Module
User Manual
ProSoft Technology, Inc.
Page 55 of 155
Checking the Nodes Exchanging Data
From the
FL-NET
submenu select
N
ODE
E
XCHANGING
D
ATA
. This screen
contains a table which indicates all nodes that are exchanging data with the
MVI56E-FLN module.
Each four-digit number in the table is a hexadecimal word (16 bits) which
represents a bit sequence that corresponds to the status of each FL-net node.
The following tables show the correlation between the bits and the nodes on the
FL-net network for the first three words.
Word
0
Bit #
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Node #
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Word
1
Bit #
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Node #
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
Word
2
Bit #
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Node #
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
The following illustration shows that Node 10 is in data exchange mode. The
value 0400 hex indicates that Bit 10 is set with a value of 1, and all other bits
have a value of 0.