![ProSoft MVI56E-FLN Скачать руководство пользователя страница 108](http://html1.mh-extra.com/html/prosoft/mvi56e-fln/mvi56e-fln_user-manual_1618868108.webp)
Reference
MVI56E-FLN ♦ ControlLogix Platform
User Manual
FA Control Network Ethernet Communication Module
Page 108 of 155
ProSoft Technology, Inc.
Own-Node Management Table
This table manages manages the local node settings.
1
The table is used to network parameter read and participation request
frames.
2
Management data is set from the FA link protocol upper layer at the node
startup time.
3
The node names and the top addresses and size of the transmitting area in
the Common Memory can be set from the network.
Table name
Size
Description
Node number
1 byte
1
to
249
(addresses 0 and 250-255 are special
function)
Common Memory Area 1 first word
2 bytes
Word address (
0
to
1FF
H
)
Common Memory Area 1 data size
2 bytes
Size (
0
to
200
H
)
Common Memory Area 2 first word
2 bytes
Word address (
0
to
1FFF
H
)
Common Memory Area 2 data size
2 bytes
Size (
0
to
2000
H
)
Upper layer status
2 bytes
RUN / STOP / ALARM / WARNING / NORMAL
See status block (page 128) for additional
information
Token watchdog time
1 byte
1
to
255
ms
Minimum frame interval time
1 byte
10
to
50
(in units of 100 ms)
Vendor code
10 bytes
Vendor code
Manufacturer model
10 bytes
Manufacture model, device name
Node name (equipment name)
10 bytes
User-defined node name
Protocol version
1 byte
80h (fixed)
FA link status
1 byte
In-ring / out-ring, and so on.
Own status
1 byte
Duplicate node number detection, and so on.