You can monitor the FA Link Status through the
FLNETSTATUS.Own_node.FA_link_status. For this example bit 0 is currently set
as 0 (MVI56E-FLN is in-ring)
Setting a value of 1 to
FLNETMODULE.CONTROL.In_Out_RingCommand
controller tag will set the MVI56E-FLN module as out-ring:
Firmware Version 1.04 or higher:
The out-ring state can be checked by the
FA Link status which now indicates that all bits are set to 0 (out-ring).
Older Versions :
The out-ring state can be checked by the FA Link status
which now indicates that bit 0 is set to 1 (out-ring).
You can observe that the LER/LE LED will be asserted to indicate that the
module was set out-ring.
Setting a value of 2 to
FLNETMODULE.CONTROL.In_Out_RingCommand
controller tag will set the MVI56E-FLN module again to in-ring:
Firmware Version 1.04 or higher
: The in-ring state can be checked by the
FA Link status which now indicates that bit 0 is set to 1 (in-ring)
Older Versions
: The in-ring state can be checked by the FA Link status
which now indicates that bit 0 is set to 0 (in-ring)
Self-Node Status
This is the information on self-node status to be given to the upper layer.
Message
Description
Self-node number conflict
Indicates the management information on node number
conflicted to see whether any node having the same node
number as the self-node setting exists on the network or not.
Token monitoring time error
Indicates the error notice information that transmit processing
has not been completed within the token monitoring time set in
the self-node.
Receive waiting status
Indicates that no frame has been received at network
initialization, being a frame receive waiting status.
Initialize error
Indicates an error is found in an initial setting or resetting
parameter.