MVI56E-FLN ♦ ControlLogix Platform
Configuring the MVI56E-FLN Module
FA Control Network Ethernet Communication Module
User Manual
ProSoft Technology, Inc.
Page 41 of 155
2
Double-click the
E
THERNET
C
ONFIGURATION
icon. This action opens the
Edit
dialog box.
3
Edit the values.
4
When you are finished editing, click
OK
to save your changes and return to
the
ProSoft Configuration Builder
main window.
Node Number
Node number
Applications
1 to 249
Used for standard FL-net (Version 2.00) devices.
250 to 254
Used for FL-net (Version 2.00) maintenance purposes.
255
Reserved for internal system use (used for broadcasting not available to
users).
0
Reserved for internal system use.
A device's node number is the last octet of its IP address.
Without a node number, the node is inoperable. If, while joining a network, a
node detects another node with an identical node number, it will not transmit any
data on the network.