![ProSoft MVI56E-FLN Скачать руководство пользователя страница 107](http://html1.mh-extra.com/html/prosoft/mvi56e-fln/mvi56e-fln_user-manual_1618868107.webp)
MVI56E-FLN ♦ ControlLogix Platform
Reference
FA Control Network Ethernet Communication Module
User Manual
ProSoft Technology, Inc.
Page 107 of 155
4.3.1 Information Tables
Types of Management Tables
Node status management is divided into the own-node management table, the
participating node management table, and the network management table.
1
The self-node management table manages the local node settings.
2
The participating node management table manages the information of the
nodes of in-ring the network.
3
The network management table manages the common network information.
The MVI56E-FLN module conforms to the mandatory items in the following
tables.
For more information refer to Status Data (page 128).
Table name
Information
Conforming level
Own-node
management
Table
Node number
Mandatory
Area 1 data top address
Optional (Supported)
Area 1 data size
Optional (Supported)
Area 2 data top address
Optional (Supported)
Area 2 data size
Optional (Supported)
Upper layer status
Mandatory
Token watchdog time
Optional (Supported)
Allowable minimum frame interval time Optional (Supported)
Vendor code
Optional
Manufacturer model name
Optional (Supported: Vendor Model)
Node name
Optional (Supported)
Protocol type
Optional (Supported)
FA link status
Mandatory
(Supported)
Own-node status
Mandatory
(Supported)
Participating node
management table
Node number
Mandatory
(Supported)
Upper layer status
Mandatory
Area 1 data top address
Mandatory
Area 1 data size
Mandatory
Area 2 data top address
Mandatory
Area 2 data size
Mandatory
Allowable refresh cycle time
Optional (Supported)
Token monitoring time
Optional (Not Supported)
Allowable minimum frame interval time Optional (Supported)
FA link status
Mandatory
Network
management table
Token holding node number
Optional (Supported)
Allowable minimum frame interval time
Mandatory
Allowable refresh cycle time
Optional (Supported)
Refresh cycle measurement time
(Current value)
Mandatory
Refresh cycle measurement time
(Maximum value)
Optional (Supported)
Refresh cycle measurement time
(Minimum value)
Optional (Supported)