Configuring the MVI56E-FLN Module
MVI56E-FLN ♦ ControlLogix Platform
User Manual
FA Control Network Ethernet Communication Module
Page 44 of 155
ProSoft Technology, Inc.
2.4
Configuring the FL-net Device
2.4.1 Setting Up the FL/ET-T-V2 Module
Setting Operation Mode Switch
Select the correct operation mode through the switch (item 3 below)
The following options are available. This procedure will consider the first option
(ID Code = C9 - 8kbytes of Link Memory Capacity)
Switch Positions
I/O module
ID Code
Link Memory
Capacity
Data Link Capacity (maximum number of
total words in reception and transmission
areas)
1 & 2 off
C9
8 kbytes
Relay link: 2048 points (128 words) (*2)
Register link: 2048 words (*1)
1 off, 2
on
D9
16 kbytes
Relay link: 2048 points (128 words) (*2)
Register link: 6144 words (* 1)
1 & 2 on
E9
32 kbytes
Relay link: 2048 points (128 words) (*2)
Register link: 8192 words (*1)
1 on, 2
off
B3
4 kbytes
The module is operated as Ethernet.