4.
Turn the 3-way valve to the "Flush" position.
Only CDLb 6 ... 55: - see figure.
1
1
2
2
3
3
B)
A)
Fig. 20: 3-way valve: A) "Flush" position; B) "Active" position
5.
Lead the tube into a collecting vessel of sufficient volume in which a
ClO
2
removal agent has been mixed, see the "Accessories" chapter.
6.
Change to the setting menu
‘Begin commissioning?’
by pressing
the
[CHANGE]
key and press the
[ENTER]
key.
7.
Enter the access code and press the
[ENTER]
key.
ð
‘Outlet v. open’
appears.
8.
Ensure that the 3-way valve is in the "Flush" position and press the
[ENTER]
key.
ð
‘Empty all vessels!’
appears and the control empties the mixer
vessel into the provided collecting vessel.
9.
As soon as
‘Vessels empty?’
appears and no more liquid runs out,
turn the 3-way valve to the "Active" position and press the
[ENTER]
key.
ð
‘Measuring vessels emptying!’
appears and the control fills the
mixer vessel in 2 steps.
10.
As soon as
‘Outlet v. open’
appears, ensure that the 3-way valve is
in the "Flush" position and press the
[ENTER]
key.
ð
‘All vessels emptying!’
appears and the control empties the
mixer vessel into the storage tank.
11.
As soon as
‘Vessels empty?’
appears and no more liquid runs out,
turn the 3-way valve to the "Active" position and press the
[ENTER]
key.
ð
‘All vessels filling!’
appears and the control fills all vessels.
12.
Empty the container holding the rinsing water into a drain, then lead
the tube back into the container.
13.
As soon as
‘Outlet v. open’
appears, ensure that the 3-way valve is
in the "Flush" position and press the
[ENTER]
key.
ð
‘All vessels emptying!’
appears and the control empties the
mixer vessel into the storage tank.
14.
As soon as
‘Vessels empty?’
appears and no more liquid runs out,
turn the 3-way valve to the "Active" position and press the
[ENTER]
key.
ð
‘Rinse system is ended!’
appears.
15.
Only CDLb 120: Secure the 3-way valve to prevent its setting being
altered.
Operation