7.2 Requirements for the water
CAUTION!
Warning of operating disruptions and corrosion damage
Severe system operating disruptions and corrosion of your
piping system can occur.
–
Always fulfil requirements in respect of the diluting water
and the water to be treated.
Parameter
Value
Temperature:
10 - 30 °C
Pressure:
3 - 6 bar
Quality:
Drinking water, particle-free, non-
corrosive
Parameter
Value*
Temperature:
0 - 60 °C
Pressure, max.
***
*** For the version "With external pre-storage module": Dependent on the
external metering pumps.
CAUTION!
Warning of too-low ClO
2
concentration
Certain dissolved matter can deplete ClO
2
.
–
Bear in mind that a depletion of ClO
2
by the matter dis‐
solved in the water can occur.
Likewise bear in mind the simultaneous formation of
chlorite.
Diluting water
Water to be treated
Requirements at the installation site