Fig. 11: Installing the hose
1
Pump suction valve
2
Nozzle
3
Clamp ring
4
Union nut
5
Hose
9.1.6 Water supply diluting water
The diluting water is fed to the system via a tube connection.
Use particle-free potable water that is non-corrosion inducing!
9.1.7 3-way valve
Only valid for Bello Zon
®
CDLb 120:
Here a 3-way valve is already mounted and installed on the
plate!
WARNING!
Warning of toxic ClO
2
solution
The venting connector (connector 3) has a blanking plug,
which must only be removed during venting or drainage.
Otherwise the inadvertent release of ClO
2
solution could
occur.
The supplied 3-way valve must be mounted on the wall as
close as possible to the Bello Zon
®
system.
Connect connector (1) with the ClO
2
outlet of the Bello Zon
®
system (if
necessary using a multifunctional valve with bracket, order no. 1027652,
connect connector (2) to the point of injection. Use PTFE tube, 6 x 4 mm
(order no. 37426)!
Installation
26