MULTI-VARIABLE MONITOR - MANUAL
33 | MVM – Manual | AntecControls.com
BACnet Network Scanning
STEP 1
Plug USB into one of the two ports on the bottom of the MVM.
STEP 2
Select
Edit in the top bar of the configurator program.
Select
Data Points in the Edit dropdown menu.
STEP 3
Right click the green
BACnet Network Scan folder.
Navigate the dropdown menu and select
Scan BACnet Network.
CAUTION
Ensure the Device ID, MS/TP Node, and MS/TP Baud Rate
have been configured before scanning for BACnet points.
Select only an interface option for the physical connections to
the MVM. If BACnet IP is not being used, then ensure it is not
enabled in green (displayed in image).