MULTI-VARIABLE MONITOR - MANUAL
27 | MVM – Manual | AntecControls.com
The MVM setup menu is accessible through the touchscreen interface. To enter the setup menu, use the default passcode of
1-6-6-4
.
NOTE:
The passcode is user configurable using the LVIS Configurator software.
TCP/IP Configuration Menu
Used to configure the TCP/IP settings for the MVM. The menu presents
information that allows the user to connect to the MVM.
Variable Name
Available
Options /
Range
Description
Address
Allows the user to set the IP address.
Netmask
Allows the user to set the netmask
address.
Gateway
Allows the user to set the gateway.
DNS (1)
DNS (2)
Allows the user to set the DNS.
NTP (1)
NTP (2)
Allows the user to set the NTP.
Ethernet Link
Shows the active Ethernet ports on the
MVM.
DHCP ON
On
Off
Allows the user to turn DHCP on or off.
Remote Config
Request Off
On
Off
Sets the remote configuration request on or
off.
NOTE:
This setting is usually set to off.
BACnet Configuration Menu
Used to configure the BACnet settings for the front-end system. This allows the
front-end system to discover all necessary points on the MVM.
Variable Name
Available
Options /
Range
Description
Device ID
1-4, 194, 303
Sets the device instance.
NOTE:
The device instance must be unique
on your building site.
MS/TP Node
1-127
Allows the user to set the BACnet MAC
address.
NOTE:
Ensure that no duplicate MAC
addresses exist on any network segment.
MS/TP Baud
9,600
19,200
38,400
78,600
Allows the user to set the baud rate.
Interface
MS/TP
BACnet/IP
Allows the user to set the method of
pulling point into the MVM.