™ PD7000 Temperature Meter
Instruction Manual
18
Display Functions & Messages
The meter displays various functions and messages
during setup, programming, and operation. The
following table shows the main menu functions and
messages in the order they appear in the menu.
Display Functions & Messages
Display
Parameter
Action/Setting
Description
setup
Setup
Enter
Setup
menu
Input
Input
Enter
Input
selection menu
tc
TC
Set meter for thermocouple
input
J, K, T, E, R, S, B, N, C
Rtd
RTD
Set meter for RTD input
100Pt, 1000Pt, 10Cu,
120Ni
A385
A385
Set meter for 0.00385
curve
A392
A392
Set meter for 0.00392
curve
F or C
F or C
Press Enter to select
degrees F or C
unitS
Units
Select the display
units/tags
Dec pt
Decimal
point
Set decimal point
dddd, dddd.d, dddd
°
F,
dddd.dF
dsplay
Display
Enter the
Display
menu
Line 1
Line 1
Press Enter to assign the
upper display parameter
(default: PV - temperature)
Line 2
Line 2
Press Enter to assign the
lower display parameter
(default: engineering units)
d-Inty
Display
intensity
Set display intensity level
from 1 to 8
RELaY
Relay
Enter the
Relay
menu
RLY 1
Relay 1
Relay 1 setup
Act 1
Action 1
Set relay 1 action
Auto
Automatic
Set relay for automatic
reset
A-nman
Auto-
manual
Set relay for automatic &
manual reset
any time
LatcH
Latching
Set relay for latching
operation
Lt-CLr
Latching-
cleared
Set relay for latching
operation with manual reset
only after alarm condition
has cleared
Altern
Alternate
Set relay for alternation
control
Sanmpl
Sampling
Set relay for sampling
operation
Display Functions & Messages
Display
Parameter
Action/Setting
Description
OFF
Off
Disable relay and front
panel status LED (Select
Off to enable Interlock
feature)
Set 1
Set 1
Program set point 1
RSt 1
Reset 1
Program reset point 1
RLY 2
Relay 2
Relays 2-8 setup
Note: Relays 5-8 are
shown only if
expansion relay module is
installed
FaiLSF
Fail-safe
Enter
Fail-safe
menu
FLS 1
Fail-safe 1
Set relay 1 fail-safe
operation
on
On
Enable fail-safe operation
off
Off
Disable fail-safe operation
FLS 2
Fail-safe 2
Set relays 2-8 fail-safe
operation
DeLAY
Delay
Enter relay
Time Delay
menu
DLY 1
Delay 1
Enter relay 1 time delay
setup
On 1
On 1
Set relay 1 On time delay
OFF 1
Off 1
Set relay 1 Off time delay
DLY 2
Delay 2
Enter relays 2-8 time delay
setup
break
Break
Set relay condition if input
break detected
ignore
Ignore
Ignore input break
condition
(Processed as an upscale
condition)
On
On
Relay goes to alarm
condition when input break
is detected
Off
Off
Relay goes to non-alarm
condition when input break
is detected
Aout
Analog
output
Enter the
Analog output
scaling menu
Dis 1
Display 1
Program display 1 value
Out 1
Output 1
Program output 1 value
(e.g. 4.000 mA)
Dis 2
Display 2
Program display 2 value
Out 2
Output 2
Program output 2 value
(e.g. 20.000 mA)
reset
Reset
Press Enter to access the
Reset
menu
Rst Hi
Reset high
Press Enter to reset max
display
Rst Lo
Reset low
Press Enter to reset min
display