™ PD7000 Temperature Meter
Instruction Manual
8
Temperature Input
Inputs
Thermocouple: J, K, T, E, R, S, B, N, C
RTD:
100 Ω platinum (0.00385 & 0.00392
coefficients
), 10 Ω copper, 120 Ω nickel,
1000 Ω platinum (0.00385 & 0.00392
coefficients)
Cold
Junction
Reference
Automatic, fixed, no user calibration
needed
Temperature
Drift
2
C maximum from 0 to 65
C ambient
temperature
4
C maximum from -20 to 0
C ambient
temperature
Offset
Adjustment
User programmable offset adjust
±50.0 degrees. This parameter allows the
user to apply an offset value to the
temperature being displayed.
Input
Impedance
Greater than 100 k
Sensor Break
Detection
Open TC or RTD sensor indicated by
display flashing
oPEn
, relays can be
programmed to go “On”, “Off”, or to “Ignore”
(Note: Ignore is detected as an upscale
condition).
Analog output goes to the programmed
sensor break value.
RTD
Averaging
Up to 10 RTDs connected in parallel can be
averaged.
Accuracy & Ranges
Type Range (°F)
Accuracy Range (°C)
Accuracy
J
-200 to 2000 ±1.8°F
-129 to 1093 ±1°C
K
-200 to 2400 ±1.8°F
-129 to 1316 ±1°C
T
-200 to 752
±1.8°F
-129 to 400
±1°C
E
-200 to 1800 ±1.8°F
-129 to 982
±1°C
R
-50 to 3000
±3.6°F
-46 to 1649
±2°C
S
-50 to 3000
±3.6°F
-46 to 1649
±2°C
B
752 to 3300
±3.6°F
400 to 1816
±2°C
N
-100 to 2300 ±3.6°F
-73 to 1260
±2°C
C
32 to 4100
±3.6°F
0 to 2260
±2°C
10
-328 to 500
±0.2°F
-200 to 260
±0.1°C
100
-328 to 1562 ±0.7°F
-200 to 850
±0.4°C
120
-110 to 500
±0.2°F
-79 to 260
±0.1°C
1000
-328 to 900
±0.7°F
-200 to 482
±0.4°C
All ranges capable of 1° or 0.1° resolution.
Relays
Rating
2 or 4 SPDT (Form C) internal and/or
4 SPST (Form A) external; rated 3 A
@ 30 VDC and 125/250 VAC resistive load;
1/14 HP (
≈
50 W) @ 125/250 VAC for
inductive loads
Noise
Suppression
Noise suppression is recommended for
each relay contact switching inductive
loads. See
Switching Inductive Loads
on
page
15
for details.
Deadband
0-100% of span, user programmable
High or Low
Alarm
User may program any alarm for high or
low trip point.
Unused alarm LEDs and relays may be
disabled (turn off).
Relay
Operation
•
Automatic (non-latching) and/or
manual reset
•
Latching (requires manual
acknowledge) with or without clear
•
Pump alternation control (2-8 relays)
•
Sampling (based on set point and
time)
•
Off (disable unused relays and enable
Interlock feature)
•
Manual on/off control mode
Relay Reset
User selectable via front panel button, F4
terminal at back of meter, external contact
closure on digital inputs, or through serial
communications.
Time Delay
0 to 999.9 seconds, on & off relay time
delays. Programmable and independent for
each relay
Fail-Safe
Operation
Programmable and independent for each
relay.
Note: Relay coil is energized in non-alarm
condition. In case of power failure, relay will
go to alarm state.
Auto
Initialization
When power is applied to the meter, relays
will reflect the state of the input to the
meter.
Additional
Relays
An external module, model
PDA1004
, is
available to add 4 SPST 3 A relays to the
meter.