55
Relative humidity
0 to 95% no condensing
Operating altitude
Up to 3,000 meters (9,843 ft) above sea level with 10% derating
per 1000m
Transit altitude
Up to 10,000 meters (32,808 ft) above sea level
Audible noise
< 50 dBA at 1 meter typical for 6kVA models
< 55 dBA at 1 meter typical for 10kVA models
Table 9. Battery
EBMs
Rack / Tower
configuration
240Vdc 20 x 12V, 7Ah
240Vdc 20 x 12V, 9Ah
192Vdc 16 x 12V, 7Ah
192Vdc 16 x 12V, 9Ah
Fuses
100A for 10kVA models and EBM
Type
Sealed, maintenance-free, valve-regulated, lead-acid, with minimum
3-year float service life at 25°C (77°F). Lifetime is reduced above 30 °C.
Monitoring
Advanced monitoring for earlier failure detection and warning
Battery port
External ANEN-SA30 connector on power module for connection to
EBM
EBM battery cable
100cm for tower models
Table 10. Communication options
Communication bay
available independent communication bay for connectivity
cards
Compatible
connectivity cards
MODBUS card
NMC card
AS400 card
Communication ports
RS-232 (DB9): 2400 bps
USB: 2400 bps
Dry out
2 pins jumper (normally closed)
Dry in
2 pins jumper (normally closed)
Emergency Power Off
3 pins jumper (normally closed)