All the previous events, alarm and fault have been recorded here. The
information includes the illustration, the event code, and the precise time of
UPS when the event happened. By press
or
<300ms, all the events
could be displayed one by one.
The max number of record is 100, when the number is larger than 100, the
latest will replace the previous.
By pressing ESC >300ms, the display would return the last main menu tree.
The control menu
By pressing
on the menu of “Control”, the display would enter the next
control menu tree.
Start Battery Test: this is one command that control the UPS to do the battery
test.
Reset Fault status: when fault occurs, UPS would keep in Fault mode and alarm.
To recover to normal status, enter this menu to reset error status, then UPS
would stop alarm and recover to bypass mode. And the reason of fault should
be checked and deleted before UPS is turned on again by manual operation.
Restore factory settings: all the settings would be recover to default factory
settings. It could only be done in Bypass mode.