28
High Efficiency
mode
The UPS is operating
on High Efficiency
mode.
Once the mains are loss or abnormal, the
UPS would transfer to Line mode or
Battery mode and the load is supplied
continuously.
1. The function could be enabled through
the LCD setting or the software
(Winpower, etc.)
2. It is reminded that the transfer time of
UPS output from HE mode to battery
mode is about 10ms. But it is still too long
for some sensitive load.
Bypass mode
Overload or fault has
occurred, or a
command has been
received, and the UPS
is in Bypass mode.
Equipment is powered but not protected
by the UPS.
Converter mode
The UPS is operating
on converter mode.
In converter mode, the UPS would free run
with fixed output frequency (50Hz or
60Hz). Once the mains is loss or abnormal,
the UPS would transfer to battery mode
and the load is supplied continuously.
1. The function could be enabled through
the LCD setting or the software
(Winpower, etc.).
2. The load should be derating to 60% in
converter mode.
Warning
There are some
abnormal problems
during the operation of
UPS. Normally the
problems are not fatal
The UPS continues working, but please pay
attention to the warning, or the UPS may
fail.
Fault
Some fatal problems
happened
The UPS will cut off the output or transfer
to bypass mode at once, and keep
alarming.