background image

 

13 

3.4 Install the UPS 

      3.4.1 Tower model: 

1.Place the unit on a flat, stable surface in its final location, 
2.Install  ‘Stabilizer bracket’(optional): remove side’s screw from the unit, then 

install ‘Stabilizer bracket’ to the unit.

   

 

3.Install  the unit to a surface(optional): place 4pcs bolts(M8 is recommended) 

to the final location previously, bolt’s position please refer to below, then fix 
the unit to the bolts.   

         

   

 

 

 

      3.4.2 RT model: 

Rack position installing 

Identify the final position and keep ‘2U’ space for this installing. 

Note that you already installed a ‘rail kit’ to rack cabinet for this operation, and 

‘1U’ rail kit is recommended to be selected. 

 

1. Install ‘Ear bracket’ to the unit by the M4 screws(flat head). 

2. Slide the unit into ‘rail kit’ and make sure tighten the ‘rack mounting screw’ . 

    

 

Note:   

Содержание VFI 10000 RTG

Страница 1: ...PowerWalker VFI 6000 TGB VFI 10000 TGB VFI 6000 TGS VFI 10000 TGS VFI 6000 RTGE VFI 10000 RTGE VFI 6000 RTG VFI 10000 RTG VFI 6000 RTGS VFI 10000 RTGS User Manual...

Страница 2: ...12 3 4 INSTALL THE UPS 13 3 5 INSTALL THE EBM 14 4 POWER CABLES CONNECTION 17 4 1 ACCESS TO TERMINAL BLOCKS AC SOURCE TO UPS 18 4 2 ACCESS TO TERMINAL BLOCKS PDU SOURCE TO R T UPS OPTIONAL 20 4 3 PARA...

Страница 3: ...43 7 1 EQUIPMENT CARE 43 7 2 TRANSPORTING THE UPS 43 7 3 STORING THE EQUIPMENT 43 7 4 REPLACING BATTERIES 44 7 5RECYCLING THE USED EQUIPMENT 46 8 TROUBLESHOOTING 46 8 1 TYPICAL ALARMS AND FAULTS 46 8...

Страница 4: ...4 IEC 61000 4 6 Electromagnetic field level 3 IEC 61000 4 8 Conducted magnetic field level 4 Special symbols The following are examples of symbols used on the UPS or accessories to alert you to import...

Страница 5: ...tions When replacing batteries replace with the same type and number of batteries or battery packs Do not dispose of batteries in a fire The batteries may explode Batteries constitute a danger electri...

Страница 6: ...the system For PLUGGABLE EQUIPMENT the socket outlet shall be installed near the equipment and shall be easily accessible Never install the system near liquids or in an excessively damp environment N...

Страница 7: ...utmost care We recommend that you take the time to read this manual to take full advantage of the many features of your UPS Uninterruptible Power System Before installing your UPS please read the book...

Страница 8: ...er failures power sags power surges brownouts line noise high voltage spikes frequency variations switching transients and harmonic distortion Power outages can occur when you least expect it and powe...

Страница 9: ...6 2 Presentation 2 1 Front panel Tower model Tower UPS 6KS 10KS Tower UPS 6K 10K Tower EBM RT model RT UPS 6K 6KS 10K 10KS UPS RT EBM...

Страница 10: ...7 2 2 Rear panels Tower model Tower UPS 6KS Tower UPS 10KS Tower UPS 6K Tower UPS 10K Tower EBM 1 Intelligent slot 2 USB 3 RS232 4 RJ11 only for RT model 5 EPO 6 Parallel card...

Страница 11: ...y connector 11 Maintenance bypass switch optional 12 EBM connector 13 EBM connector 14 Fuse board cover replace EBM fuse RT model RT UPS 6K 6KS 10K 10KS RT EBM 1 Intelligent slot 2 Dry IN OUT 3 USB 4...

Страница 12: ...9 EBM fuse 14 EBM plug 15 EBM connector 2 3 Circuit diagram...

Страница 13: ...amaged during shipment keep the shipping cartons and packing materials for the carrier or place of purchase and file a claim for shipping damage If you discover damage after acceptance file a claim fo...

Страница 14: ...PS RT EBM Note The cabinet is heavy please see spec weight provided on the carton label Do not lift the unit s front panel and rear panel Discard or recycle the packaging in a responsible manner or st...

Страница 15: ...e unit Tower UPS 6K 10K Tower UPS 6KS 10KS Tower EBM RT UPS 6K 10K RT UPS 6KS 10KS RT EBM Battery power cable V USB cable V V V V RS232 cable O O O O Parallel cable V V V V Dry contractor V V V V EPO...

Страница 16: ...ecommended to the final location previously bolt s position please refer to below then fix the unit to the bolts 3 4 2 RT model Rack position installing Identify the final position and keep 2U space f...

Страница 17: ...bilizer bracket 3 5 Install the EBM Tower EBM installation 1 Place the unit on a flat stable surface in its final location 2 Install Stabilizer bracket optional remove the side s screw from the unit t...

Страница 18: ...ease check the Voltage parameter on rear panel if it matches the UPS before connection The battery number can be adjusted from 16pcs 2 strings to 20pcs 2 strings for this unit if you ordered other typ...

Страница 19: ...ble for 19 inch rack cabinet installation with a minimum of 800mm depth 3 Plug Battery power cable to UPS s external battery connector Note This Battery power cable may have different plug according t...

Страница 20: ...g additional unit place it next to the previous unit in their final location 4 Power cables connection Recommended protective devices and cable cross sections Recommended upstream protection UPS power...

Страница 21: ...to terminal blocks AC source to UPS High leakage current Earth connection essential before connecting supply Common input output sources connection This type of connection must be carried out by quali...

Страница 22: ...19 2 Connect the AC cable to terminal blocks refer to the indication on rear panel Tower model R T model 3 Tie up the AC cable to the rear panel 4 Install back the cover of terminal block...

Страница 23: ...ct the UPS s terminal blocks from PDU s source detail operation please refer to PDU s user manual 4 3 Parallel Installation and Operation As long as the UPS is equipped with parallel board and paralle...

Страница 24: ...pendent battery packs for each UPS 3 Remove the cover plate of parallel port on the UPS connect each UPS one by one with parallel cable and make sure the cable is screwed tightly Note The length of pa...

Страница 25: ...V turn off the input breakers to let UPS shut down And then switch on the output breakers for all the UPS 9 Turn on the input breakers for the parallel UPS Pressing button continuously for more than 1...

Страница 26: ...s mode 7 Switch on the O P breakers and main O P breaker transfer the main maintenance switch or static switch from BPS to UPS 8 Press the button of one UPS all the ups will turn on after that the sys...

Страница 27: ...information about the UPS itself load status events measurements and settings The following table shows the indicator status and description Indicator Status Description Normal Green On The UPS is op...

Страница 28: ...his button for 1s to stop alarm and clear fault Scroll up Press this button for 100ms 1s to scroll up the menu option Scroll down Press this button for 100ms 1s to scroll down the menu option Enter ne...

Страница 29: ...will work again The Buzzer definition as below UPS condition Buzzer status Fault active Continuous Over Load Warning active 2 Beep every second Other Warning active Beep every second Battery output Be...

Страница 30: ...equipment Battery mode 1 beep every 4 seconds A utility failure has occurred and the UPS is on Battery mode The UPS is powering the equipment with the battery power Prepare your equipment for shutdown...

Страница 31: ...is powered but not protected by the UPS Converter mode The UPS is operating on converter mode In converter mode the UPS would free run with fixed output frequency 50Hz or 60Hz Once the mains is loss...

Страница 32: ...uttons and to scroll through the menu structure Press the Enter button to select an option Press the ESC button to cancel or return to the previous menu When starting the UPS the display is in the def...

Страница 33: ...disabled Enabled disabled Audible alarm enabled disabled enabled Output voltage 208V 220V 230V 240V Can be changed in Standby mode and Bypass mode 230V Output autosensing 50HZ 60HZ autosensing Power...

Страница 34: ...heck all the connection is correct Power on the UPS the fan begins to rotate After that the LCD will show the default UPS status summary screen Pressing button continuously for more than 1 second the...

Страница 35: ...down and no output voltage is available from the UPS output terminal UPS shutdown without utility To shut down the UPS without utility To power off the UPS by pressing button continuously for more th...

Страница 36: ...enu The UPS status menu By pressing on the menu of UPS status the display would enter the next UPS status menu tree The content of UPS status menu tree is same as the default UPS status summary menu B...

Страница 37: ...d enter the next measurement menu tree A lot of detailed useful information could be checked here Ex the output voltage and frequency the output current the load capacity the input voltage and frequen...

Страница 38: ...35 The event log menu By pressing on the menu of Event log the display would enter the next event menu tree...

Страница 39: ...ee The control menu By pressing on the menu of Control the display would enter the next control menu tree Start Battery Test this is one command that control the UPS to do the battery test Reset Fault...

Страница 40: ...37...

Страница 41: ...The setting menu Please contact your local distributor for further information before using the settings Some settings would be changed the specification and some settings would enable or disable some...

Страница 42: ...39...

Страница 43: ...V By press 1s The option would flash Output voltage 230V By press 1s Setting menu tree Output voltage 220V By press or 100ms to select the wanted option Output voltage 220V By press 1s to confirm the...

Страница 44: ...ovides an emergence power off function When the EPO function is enabled default setting once the EPO port is pulled out the UPS would shut off the output and enter into EPO mode and the UPS would not...

Страница 45: ...eb browser interface connects to a twisted pair Ethernet 10 100BaseT network In addition 2 This series UPS has AS400 card an optional accessory for AS400 communication protocol Please contact your loc...

Страница 46: ...service life The length of service life varies depending on the frequency of usage and ambient temperature Batteries used beyond expected service life will often have severely reduced runtimes Replac...

Страница 47: ...ings or other metal objects 2 Use tools with insulated handles 3 Do not lay tools or metal parts on top of batteries 4 Wear rubber gloves and boots When replacing batteries replace with the same type...

Страница 48: ...l EBM s are installed unplug the EBM power cable from each EBM 2 Replace the EBM s See Recycling the used equipment refer to chapter 7 4 for proper disposal A small amount of arcing may occur when con...

Страница 49: ...enter 8 Troubleshooting The UPS is designed for durable automatic operation and also alert you whenever potential operating problems may occur Usually the alarms shown by the control panel do not mean...

Страница 50: ...o battery Fault Red LED is Flash 1beep every 1 second Code A011 The batteries are disconnected Verify that all batteries are properly connected If the condition persists contact your service represent...

Страница 51: ...nded out of bypass Check the maintain bypass switch status In HE Mode Line green LED is on Code E063 The UPS is on bypass while operating on the High Efficiency setting The equipment transferred to by...

Страница 52: ...is short circuit Ensure short circuit is removed before turning on again Fan Failure Fault Red LED is flash 1 beep every 1 second Code A085 Indicates that the fan could not work normally Check fans of...

Страница 53: ...ssfully Contact your service representative Charger Fail Fault Red LED is flash 1 beep every 1 second Code A015 Indicates that the UPS has confirmed the charger has failed The UPS turns off the charge...

Страница 54: ...different not allow turn on UPS Keep rate power be the same HE in parallel Fault Red LED is flash 1 beep every 1 second Code A0EB Parallel system UPS mode set as HE HE not allow in parallel system cha...

Страница 55: ...25 589 452 VFI 6000 TGS 13 225 348 452 VFI 10000 TGS 15 2 225 348 452 Tower EBM 16 2 BAT 84 6 225 589 452 Tower EBM 20 2 BAT 102 225 589 452 VFI 6000 RTG 13 438 86 573 VFI 10000 RTG 14 7 438 86 573 VF...

Страница 56: ...Tower 6K 6KS Hardwired Not provided RT 6K 6KS Tower 10K 10KS RT 10K 10KS Table 6 Electrical output All models Normal mode Battery mode Voltage regulation 1 1 Efficiency 98 High Efficiency mode 95 93 F...

Страница 57: ...EC EN 62040 2 Cat C2 IEC EN 62040 3 EN 60950 1 EMC Emissions IEC 61000 3 2 3 12 IEC 61000 3 3 3 11 EMC Immunity IEC 61000 2 2 IEC 61000 4 2 Level 4 IEC 61000 4 3 Level 3 IEC 61000 4 4 Level 4 also on...

Страница 58: ...aintenance free valve regulated lead acid with minimum 3 year float service life at 25 C 77 F Lifetime is reduced above 30 C Monitoring Advanced monitoring for earlier failure detection and warning Ba...

Страница 59: ...pplied by the UPS operating on battery power HE mode Operating mode by which the load is supplied directly by the AC source if it is within the tolerances defined by the user This mode reduces the con...

Отзывы: