50
BUS Softstart Fail
Fault (Red) LED is On.
Beep continuous.
Code: F025
Indicates that the BUS could
not soft start successfully
Contact your service
representative
Inv Over Voltage
Fault (Red) LED is On.
Beep continuous.
Code: F032
Indicates that the UPS get
invert over voltage fault
The UPS transfers to
Bypass mode if supporting
the load
Inv Under Voltage
Fault (Red) LED is On.
Beep continuous.
Code: F033
Indicates that the UPS get
inverter under voltage fault
The UPS transfers to
Bypass mode if supporting
the load
Inv Softstart Fail
Fault (Red) LED is On.
Beep continuous.
Code: F034
Indicates that the inverter
could not soft start successfully
Contact your service
representative
Charger Fail
Fault (Red) LED is
flash
1 beep every 1 second
Code: A015
Indicates that the UPS has
confirmed the charger has
failed
The UPS turns off the
charger until the next
power recycle. Contact
your service representative
Battery Over Voltage
Fault (Red) LED is On.
Beep continuous.
Code: F016
Indicates that the battery
voltage is too high
The UPS will turn off the
charger until the battery
voltage is normal
Negative power Fault
Fault (Red) LED is On.
Beep continuous.
Code: F0E1
In parallel system
,
power of
UPS is negative
Redundancy mode
,
the
fault UPS turn to fault
mode without output
Increase mode
,
UPS1&
UPS2 turn to fault mode
Parallel cable loss
Fault (Red) LED is On.
Beep continuous.
Code: F0E2
In parallel system
,
parallel
cable disconnect
Disconnect parallel cable
one turn to fault mode