18
Protective earthing conductor
Min cross section
6mm^2 (8AWG)
10mm^2 (6AWG)
Input L, N, G
Min conductor cross section
6mm^2 (8AWG)
10mm^2(6AWG)
Input fuse
80A
100A
Output L,N,
Min conductor cross section
6mm^2 (8AWG)
10mm^2(6AWG)
4.1
Access to terminal blocks(AC source to UPS)
High leakage current:
Earth connection essential before connecting supply.
Common input/output sources connection
This type of connection must be carried out by qualified electrical personnel
Before carrying out any connection, check that the upstream protection devices
(Normal AC source and Bypass AC source) are open "O" (Off).
Always connect the ground wire first
1. Remove the cover of terminal block.