![PowerWalker VFI 10000 RTG Скачать руководство пользователя страница 54](http://html1.mh-extra.com/html/powerwalker/vfi-10000-rtg/vfi-10000-rtg_user-manual_1591944054.webp)
51
Parallel system battery
status
Fault (Red) LED is flash
1 beep every 1 second
Code: A0E6
UPS1 connect battery
,
UPS2
without battery
Check battery connect
status
Line input different
Fault (Red) LED is flash
1 beep every 1 second
Code: A0E7
Parallel system
,
UPS1 line ok
,
UPS2 line loss
Check the line input
Power strategy different
Fault (Red) LED is flash
1 beep every 1 second
Code: A0E9
Parallel system
,
UPS mode
(
normal
,
converter
,
HE
)
different
Check UPS OP mode, Keep
OP mode be the same
Rate power different
Fault (Red) LED is flash
1 beep every 1 second
Code: A0EA
Parallel system rate power
different
Rate power different
,
not
allow turn on UPS. Keep
rate power be the same
HE in parallel
Fault (Red) LED is flash
1 beep every 1 second
Code: A0EB
Parallel system
,
UPS mode set
as HE
HE not allow in parallel
system
,
change UPS mode
8.2 Silencing the alarm
Press the ESC (Escape) button 3s on the front panel display to silence the alarm.
Check the alarm condition and perform the applicable action to resolve the
condition. If the alarm status changes or press the ESC button 3s on the front
panel dispaly, the alarm beeps again, overriding the previous alarm silencing.
9. Specifications
9.1 Model specifications
Table 1. Power Module model list
Model
Power Ratings
VFI 6000 TGB
6000VA / 6000W
VFI 10000 TGB
10000VA / 10000W
VFI 6000 TGS
6000VA / 6000W
VFI 10000 TGS
10000VA / 10000W
VFI 6000 RTG
6000VA / 6000W
VFI 10000 RTG
10000VA / 10000W
Содержание VFI 10000 RTG
Страница 12: ...9 EBM fuse 14 EBM plug 15 EBM connector 2 3 Circuit diagram...
Страница 38: ...35 The event log menu By pressing on the menu of Event log the display would enter the next event menu tree...
Страница 40: ...37...
Страница 42: ...39...