47
Battery mode
Battery(Orange) LED is
On.
1 beep every 4 seconds.
Code: E062
A utility failure has occurred
and the UPS is in Battery mode.
The UPS is powering the
equipment with battery
power. Prepare your
equipment for shutdown.
Battery low
Battery(Orange) LED is
On.
1 beep every 1 second.
Code: A012
The UPS is in Battery mode and
the battery is running low.
This warning is
approximate, and the
actual time to shutdown
may vary significantly.
Depending on the UPS
load and number of
Extended Battery Modules
(EBMs), the "Battery Low"
warning may occur before
the batteries reach 20%
capacity.
No battery
Fault (Red) LED is Flash
1beep every 1 second
Code: A011
The batteries are disconnected.
Verify that all batteries are
properly connected.
If the condition persists,
contact your service
representative.
Bypass mode
Bypass (Orange) LED is
on.
Code: E060
An overload or a fault has
occurred, or a command has
been received and the UPS is in
Bypass mode
Equipment is powered but
not protected by the UPS.
Check for one of the
following alarms: over
temperature, overload or
UPS failure.
Power overload
Fault (Red) LED is Flash
2beep every 1 second
Code: A041
Power requirements exceed
the UPS capacity
Remove some of the
equipment from the UPS.
The UPS continues to
operate, but may switch to
Bypass mode or shut down
if the load increases.
The alarm resets when the
condition becomes
inactive.