background image

25 

 

 

4. Trouble Shooting 

If the UPS system does not operate correctly, please solve the problem by using the table below.   

Symptom 

Possible cause 

Remedy 

No  indication  and  alarm  in  the  front 

display panel even though the mains is 

normal.   

The  AC  input  power  is  not 

connected well. 

Check  if  input  cable  firmly 

connected to the mains.   

The  icon 

and  the  warning  code 

  flash on LCD display and alarm 

beeps every second. 

EPO function is enabled. 

Set  the  circuit  in  closed 

position  to  disable  EPO 

function.   

The icon 

and 

  flash on LCD 

display and alarm beeps every second. 

The  external  or  internal 

battery 

is 

incorrectly 

connected. 

Check  if  all  batteries  are 

connected well. 

The  icon 

  and

  flash  on  LCD 

display  and  alarm  beeps  twice  every 

second. 

UPS is overload.   

Remove excess loads from UPS 

output. 

UPS  is  overloaded.  Devices 

connected  to  the UPS  are  fed 
directly  by  the  electrical 

network via the Bypass. 

Remove excess loads from UPS 
output. 

After  repetitive  overloads,  the 

UPS  is  locked  in  the  Bypass 

mode.  Connected  devices  are 

fed directly by the mains. 

Remove excess loads from UPS 

output  first.  Then  shut  down 

the UPS and restart it. 

Fault  code  is  shown  as  43.  The  icon 

  lights  on  LCD  display  and  alarm 

beeps continuously. 

UPS  is  overload  too  long  and 

becomes fault. Then UPS shut 

down automatically. 

Remove excess loads from UPS 

output and restart it. 

Fault  code  is  shown  as  14  and  alarm 

beeps continuously. 

The 

UPS 

shut 

down 

automatically  because  short 

circuit  occurs  on  the  UPS 

output. 

Check  output  wiring  and  if 

connected devices are in short 

circuit status. 

Fault code is shown as 01, 02, 03, 04, 

11, 12, 13, 14,1A, 21, 24, 41, 42 or 43 

on  LCD  display  and  alarm  beeps 

continuously. 

A  UPS  internal  fault  has 

occurred.  There  are  two 

possible results: 

1. The load is still supplied, but 

directly  from  AC  power  via 

bypass.   

2.  The  load  is  no  longer 

supplied by power.   

Contact your dealer. 

Battery  backup  time  is  shorter  than 

nominal value 

Batteries are not fully charged 

Charge  the  batteries  for  at 

least  7  hours  and  then  check 

capacity.  If  the  problem  still 

persists, consult your dealer.   

Batteries defect 

Contact your dealer to replace 

the battery. 

The icon 

and 

  flash on LCD 

display and alarm beeps every second. 

Fan  is  locked  or  not  working; 

or the UPS temperature is too 

high. 

Check fans and notify dealer.   

 

Содержание Centurion RT 6000VA

Страница 1: ......

Страница 2: ...instructions in this manual strictly Save this manual properly and read carefully the following instructions before installing the unit Do not operate this unit before reading through all safety info...

Страница 3: ...INSTALLATION 6 2 5 UPS INSTALLATION FOR PARALLEL SYSTEM 8 2 5 SOFTWARE INSTALLATION 8 3 OPERATIONS 9 3 1 BUTTON OPERATION 9 3 2 LED INDICATORS AND LCD PANEL 9 3 3 AUDIBLE ALARM 11 3 4 SINGLE UPS OPERA...

Страница 4: ...nect appliances or devices which would overload the UPS e g big motor type equipment to the UPS output sockets or terminal Place cables in such a way that no one can step on or trip over them Do not b...

Страница 5: ...inals may be live when the UPS is not connected to an AC supply 1 5 Operation Do not disconnect the earth conductor cable on the UPS or the building wiring terminals in any time since this would cance...

Страница 6: ...00 4 3 Level 3 EFT IEC EN 61000 4 4 Level 4 SURGE IEC EN 61000 4 5 Level 4 CS IEC EN 61000 4 6 Level 3 Power frequency Magnetic field IEC EN 61000 4 8 Level 4 Low Frequency Signals IEC EN 61000 2 2 Wa...

Страница 7: ...y available for parallel model One share current cable only available for parallel model One battery cable option NOTE Before installation please inspect the unit Be sure that nothing inside the packa...

Страница 8: ...n be used to tower install the UPS module in 2U or UPS module with one battery bank in 4U Install UPS module in 2U Assemble two feet and one short extension as one tower stand shown in step 1 Align th...

Страница 9: ...city of UPS to avoid the hazards of electric shock or fire NOTE Do not use the wall receptacle as the input power source for the UPS as its rated current is less than the UPS s maximum input current O...

Страница 10: ...tall it carefully Switch off the battery breaker before installation Warning For standard battery pack there is one DC breaker to disconnect the battery pack and the UPS But for other external battery...

Страница 11: ...h UPS is connected to an independent battery pack 5 Remove the cover of parallel share current cable port on the UPS connect each UPS one by one with the parallel cable and share current cable and the...

Страница 12: ...isplay next selection in setting menu Mute Down Button Mute the alarm Press and hold the button more than 0 5s to mute the buzzer Please refer to section 3 4 9 for details Down key Press this button t...

Страница 13: ...ltage A ampere percent centigrade degree Hz frequency AC alternating current DC direct current Indicate the output voltage output frequency load current and load percentage k kilo W watt V voltage A a...

Страница 14: ...e UPS will operate in Battery mode without interruption NOTE When the UPS is running out battery it will shut down automatically at Battery mode When the utility power is restored the UPS will auto re...

Страница 15: ...no more load to be switched off at that time you have to shut down all loads as soon as possible to protect the devices or save data Otherwise there is a risk of data loss or load failure 2 In Battery...

Страница 16: ...ble shooting table in chapter 4 for details 2 Please check the loads wiring ventilation utility battery and so on after the fault occurs Don t try to turn on the UPS again before solving the problems...

Страница 17: ...Program 15 section 3 7 in LCD setting If voltage difference remains more than 1 5V after calibration please contact your local distributor or service center for help 2 Calibrate the output voltage me...

Страница 18: ...unit 3 After it shuts down you can turn off the battery breaker for long run model and remove the parallel cable and share current cable Then remove the unit from the parallel system Second method 1...

Страница 19: ...ameter 1 There are three parameters to set up the UPS Parameter 1 It s for program alternatives Refer to below table Parameter 2 3 It s is the setting options or values for program Programs available...

Страница 20: ...ameter 2 50 0Hz The output frequency is setting for 50 0Hz 60 0Hz The output frequency is setting for 60 0Hz At If selected output frequency will be decided according to the latest normal utility freq...

Страница 21: ...range is from 51 0Hz to 54 0 Hz 60 Hz Setting range is from 61 0Hz to 64 0Hz The default value is 54 0Hz 64 0Hz 05 ECO mode enable disable Interface Setting Parameter 3 Enable or disable ECO function...

Страница 22: ...utomatic bypass is acceptable but manual bypass is not allowed Manual bypass means users manually operate UPS for Bypass mode For example pressing OFF button in AC mode to turn into Bypass mode 09 Bat...

Страница 23: ...0V to 5 7V the default value is 0V 14 Charger voltage adjustment Interface Setting Parameter 2 you may choose Add or Sub to adjust charger voltage Parameter 3 the voltage range is from 0V to 9 9V the...

Страница 24: ...2 battery numbers setting Set the battery numbers ranging from 16 20 After pressing Enter button to confirm selection then it will show charger status in Parameter 1 Parameter 3 charger status settin...

Страница 25: ...LCD display CVCF mode Description When input frequency is within 46 to 64Hz the UPS can be set at a constant output frequency 50 Hz or 60 Hz The UPS will still charge battery under this mode LCD displ...

Страница 26: ...t code Icon Bus start failure 01 None Battery SCR short circuited 21 None Bus over 02 None Inverter relay short circuited 24 None Bus under 03 None Charger short circuited 2a None Bus unbalance 04 Non...

Страница 27: ...ry second Battery unconnected Beeping every second 3 11 Warning Code Warning code Warning event Warning code Warning event 01 Battery unconnected 10 L1 IP fuse broken 07 Over charge 21 Line situations...

Страница 28: ...Remove excess loads from UPS output first Then shut down the UPS and restart it Fault code is shown as 43 The icon lights on LCD display and alarm beeps continuously UPS is overload too long and beco...

Страница 29: ...required precautionary measures may replace batteries and supervise operations Unauthorized persons must be kept well away from the batteries Verify that no voltage between the battery terminals and...

Страница 30: ...27 6 Specifications...

Страница 31: ...ing and inspection charge will apply as above 11 For hardwired products larger than 3KVA the warranty covers onsite repair for metro areas in capital cities only For equipment installed in remote loca...

Отзывы: