finished the startup, there will be a few seconds of voltage pulse (same as the input voltage) 
on the bypass output. If you need to remove the pulse on this mode to protect your load better, 
you could contact the dealer for help.   
For the UPS with parallel function, this pulse situation won’t happen.
 

 

03: Voltage range for bypass   

Interface 

Setting 

 

Parameter 2: Set the acceptable low voltage for bypass. Setting 

range is from 110V to 209V and the default value is 110V. 

Parameter 3: Set the acceptable high voltage for bypass. Setting 

range is from 231V to 276V and the default value is 264V. 

 

04: Frequency range for bypass 

Interface 

Setting 

 

Parameter 2: Set the acceptable low frequency for bypass.   

50 Hz system: Setting range is from 46.0Hz to 49.0Hz. 

60 Hz system: Setting range is from 56.0Hz to 59.0Hz. 

The default value is 46.0Hz/56.0Hz. 

Parameter 3: Set the acceptable high frequency for bypass.   

50 Hz: Setting range is from 51.0Hz to 54.0 Hz.   

60 Hz: Setting range is from 61.0Hz to 64.0Hz. 

The default value is 54.0Hz/64.0Hz. 

 

05: ECO mode enable/disable 

Interface 

Setting 

 

Parameter 3: Enable or disable ECO function. You may choose 

following two options: 

DIS: disable ECO function   

ENA: enable ECO function   

If ECO function is disabled, voltage range and frequency range for 

ECO mode still can be set, but it is meaningless unless the ECO 

function is enabled. 

 

06: Voltage range for ECO mode 

Interface 

Setting 

 

Parameter 2: Low voltage point in ECO mode. The setting range 

is from 5% to 10% of the nominal voltage. 

Parameter 3: High voltage point in ECO mode. The setting range 

is from 5% to 10% of the nominal voltage. 

 

07: Frequency range for ECO mode 

Interface 

Setting 

 

Parameter 2: Set low frequency point for ECO mode. 

50 Hz system: Setting range is from 46.0Hz to 48.0Hz. 

60 Hz system: Setting range is from 56.0Hz to 58.0Hz. 

The default value is 48.0Hz/58.0Hz. 

Parameter 3: Set high frequency point for ECO mode.   

50 Hz: Setting range is from 52.0Hz to 54.0 Hz.   

60 Hz: Setting range is from 62.0Hz to 64.0Hz. 

The default value is 52.0Hz/62.0Hz. 

Содержание Centurion RT 6000VA

Страница 1: ......

Страница 2: ...instructions in this manual strictly Save this manual properly and read carefully the following instructions before installing the unit Do not operate this unit before reading through all safety info...

Страница 3: ...INSTALLATION 6 2 5 UPS INSTALLATION FOR PARALLEL SYSTEM 8 2 5 SOFTWARE INSTALLATION 8 3 OPERATIONS 9 3 1 BUTTON OPERATION 9 3 2 LED INDICATORS AND LCD PANEL 9 3 3 AUDIBLE ALARM 11 3 4 SINGLE UPS OPERA...

Страница 4: ...nect appliances or devices which would overload the UPS e g big motor type equipment to the UPS output sockets or terminal Place cables in such a way that no one can step on or trip over them Do not b...

Страница 5: ...inals may be live when the UPS is not connected to an AC supply 1 5 Operation Do not disconnect the earth conductor cable on the UPS or the building wiring terminals in any time since this would cance...

Страница 6: ...00 4 3 Level 3 EFT IEC EN 61000 4 4 Level 4 SURGE IEC EN 61000 4 5 Level 4 CS IEC EN 61000 4 6 Level 3 Power frequency Magnetic field IEC EN 61000 4 8 Level 4 Low Frequency Signals IEC EN 61000 2 2 Wa...

Страница 7: ...y available for parallel model One share current cable only available for parallel model One battery cable option NOTE Before installation please inspect the unit Be sure that nothing inside the packa...

Страница 8: ...n be used to tower install the UPS module in 2U or UPS module with one battery bank in 4U Install UPS module in 2U Assemble two feet and one short extension as one tower stand shown in step 1 Align th...

Страница 9: ...city of UPS to avoid the hazards of electric shock or fire NOTE Do not use the wall receptacle as the input power source for the UPS as its rated current is less than the UPS s maximum input current O...

Страница 10: ...tall it carefully Switch off the battery breaker before installation Warning For standard battery pack there is one DC breaker to disconnect the battery pack and the UPS But for other external battery...

Страница 11: ...h UPS is connected to an independent battery pack 5 Remove the cover of parallel share current cable port on the UPS connect each UPS one by one with the parallel cable and share current cable and the...

Страница 12: ...isplay next selection in setting menu Mute Down Button Mute the alarm Press and hold the button more than 0 5s to mute the buzzer Please refer to section 3 4 9 for details Down key Press this button t...

Страница 13: ...ltage A ampere percent centigrade degree Hz frequency AC alternating current DC direct current Indicate the output voltage output frequency load current and load percentage k kilo W watt V voltage A a...

Страница 14: ...e UPS will operate in Battery mode without interruption NOTE When the UPS is running out battery it will shut down automatically at Battery mode When the utility power is restored the UPS will auto re...

Страница 15: ...no more load to be switched off at that time you have to shut down all loads as soon as possible to protect the devices or save data Otherwise there is a risk of data loss or load failure 2 In Battery...

Страница 16: ...ble shooting table in chapter 4 for details 2 Please check the loads wiring ventilation utility battery and so on after the fault occurs Don t try to turn on the UPS again before solving the problems...

Страница 17: ...Program 15 section 3 7 in LCD setting If voltage difference remains more than 1 5V after calibration please contact your local distributor or service center for help 2 Calibrate the output voltage me...

Страница 18: ...unit 3 After it shuts down you can turn off the battery breaker for long run model and remove the parallel cable and share current cable Then remove the unit from the parallel system Second method 1...

Страница 19: ...ameter 1 There are three parameters to set up the UPS Parameter 1 It s for program alternatives Refer to below table Parameter 2 3 It s is the setting options or values for program Programs available...

Страница 20: ...ameter 2 50 0Hz The output frequency is setting for 50 0Hz 60 0Hz The output frequency is setting for 60 0Hz At If selected output frequency will be decided according to the latest normal utility freq...

Страница 21: ...range is from 51 0Hz to 54 0 Hz 60 Hz Setting range is from 61 0Hz to 64 0Hz The default value is 54 0Hz 64 0Hz 05 ECO mode enable disable Interface Setting Parameter 3 Enable or disable ECO function...

Страница 22: ...utomatic bypass is acceptable but manual bypass is not allowed Manual bypass means users manually operate UPS for Bypass mode For example pressing OFF button in AC mode to turn into Bypass mode 09 Bat...

Страница 23: ...0V to 5 7V the default value is 0V 14 Charger voltage adjustment Interface Setting Parameter 2 you may choose Add or Sub to adjust charger voltage Parameter 3 the voltage range is from 0V to 9 9V the...

Страница 24: ...2 battery numbers setting Set the battery numbers ranging from 16 20 After pressing Enter button to confirm selection then it will show charger status in Parameter 1 Parameter 3 charger status settin...

Страница 25: ...LCD display CVCF mode Description When input frequency is within 46 to 64Hz the UPS can be set at a constant output frequency 50 Hz or 60 Hz The UPS will still charge battery under this mode LCD displ...

Страница 26: ...t code Icon Bus start failure 01 None Battery SCR short circuited 21 None Bus over 02 None Inverter relay short circuited 24 None Bus under 03 None Charger short circuited 2a None Bus unbalance 04 Non...

Страница 27: ...ry second Battery unconnected Beeping every second 3 11 Warning Code Warning code Warning event Warning code Warning event 01 Battery unconnected 10 L1 IP fuse broken 07 Over charge 21 Line situations...

Страница 28: ...Remove excess loads from UPS output first Then shut down the UPS and restart it Fault code is shown as 43 The icon lights on LCD display and alarm beeps continuously UPS is overload too long and beco...

Страница 29: ...required precautionary measures may replace batteries and supervise operations Unauthorized persons must be kept well away from the batteries Verify that no voltage between the battery terminals and...

Страница 30: ...27 6 Specifications...

Страница 31: ...ing and inspection charge will apply as above 11 For hardwired products larger than 3KVA the warranty covers onsite repair for metro areas in capital cities only For equipment installed in remote loca...

Отзывы: