12 

 

for system safety.   

5)    If  the  overload  time  is  longer  than  acceptable  time  listed  in  spec  at  AC  mode,  the  UPS  will 

automatically transfer to Bypass mode.    After the overload is removed, it will return to AC mode. If 
the  overload  time  is  longer  than  acceptable  time  listed  in  spec  at  Battery  mode,  the  UPS  will 
become fault status. At this time, if bypass is enabled and the voltage and frequency in the range of 
it is set value, the UPS will power to the load via bypass. If bypass function is disabled or the input 
power is not within bypass acceptable range, it will cut off output directly. 

3-4-4. Charge the batteries 

1)    After the UPS is connected to the utility power and working on the AC mode, the charger will charge 

the batteries automatically except in Battery mode or during battery self-test.   

2)    Suggest  to  charge  batteries  at  least  10  hours  before  use.  Otherwise,  the  backup  time  may  be 

shorter than expected time. 

3)    Make sure the battery numbers setting on the control board (Please refer to the section 3-4-12 for 

detailed setting) is consistent to real connection. 

3-4-5. Battery mode operation 

1)    When the UPS is in Battery mode, the buzzer will beep according to different battery capacity. If the 

battery  capacity  is  more  than  25%,  the  buzzer  will  beep  once  every  4  seconds;  If  the  battery 
voltage drops to the alarm level, the buzzer will beep quickly (once every sec) to remind users that 
the battery is at low level and the UPS will shut down automatically soon. Users could switch off 
some non-critical loads to disable the shutdown alarm and prolong the backup time. If there is no 
more load to be switched off at that time, you have to shut down all loads as soon as possible to 
protect the devices or save data. Otherwise, there is a risk of data loss or load failure.   

2)    In Battery mode, if buzzer sound annoys, users can press the Mute button to disable the buzzer. 

3)    The backup time of the long-run model depends on the external battery capacity. 

4)    The backup time may vary from different environment temperature and load type. 

5)    When setting backup time for 16.5 hours (990min in LCD setting menu 09), after discharging 16.5 

hours, UPS will shut down automatically to protect the battery. This battery discharge protection 
can be enabled or disabled through LCD panel control. (Refer to 3-7 LCD setting section) 

3-4-6. Test the batteries 

1)    If you need to check the battery status when the UPS is running in AC mode/CVCF mode/ECO mode, 

you could press the “Test” button to let the UPS do battery self-test. 

2)    To keep the system reliable, the UPS can perform the battery self-test periodically while connect the 

monitoring software. 

3)    Users also can set battery self-test through monitoring software. 

4)    If  the UPS  is  at  battery  self-test,  the  LCD display and buzzer  indication  will be  the  same  as  at 

Battery mode except that the battery LED is flashing. 

3-4-7. Turn off the UPS with utility power supply in AC mode 

1)    Turn off the inverter of the UPS by pressing “OFF” button for at least 0.5s, and then the buzzer will 

beep once. The UPS will turn into Bypass mode.   

NOTE 1: If the UPS has been set to enable the bypass output, it will bypass voltage from utility 
power to output terminal even though you have turned off the UPS (inverter). 

NOTE 2: After turning off the UPS, please be aware that the UPS is working at Bypass mode and 
there is risk of power loss for connected devices.   

Содержание Centurion RT 6000VA

Страница 1: ......

Страница 2: ...instructions in this manual strictly Save this manual properly and read carefully the following instructions before installing the unit Do not operate this unit before reading through all safety info...

Страница 3: ...INSTALLATION 6 2 5 UPS INSTALLATION FOR PARALLEL SYSTEM 8 2 5 SOFTWARE INSTALLATION 8 3 OPERATIONS 9 3 1 BUTTON OPERATION 9 3 2 LED INDICATORS AND LCD PANEL 9 3 3 AUDIBLE ALARM 11 3 4 SINGLE UPS OPERA...

Страница 4: ...nect appliances or devices which would overload the UPS e g big motor type equipment to the UPS output sockets or terminal Place cables in such a way that no one can step on or trip over them Do not b...

Страница 5: ...inals may be live when the UPS is not connected to an AC supply 1 5 Operation Do not disconnect the earth conductor cable on the UPS or the building wiring terminals in any time since this would cance...

Страница 6: ...00 4 3 Level 3 EFT IEC EN 61000 4 4 Level 4 SURGE IEC EN 61000 4 5 Level 4 CS IEC EN 61000 4 6 Level 3 Power frequency Magnetic field IEC EN 61000 4 8 Level 4 Low Frequency Signals IEC EN 61000 2 2 Wa...

Страница 7: ...y available for parallel model One share current cable only available for parallel model One battery cable option NOTE Before installation please inspect the unit Be sure that nothing inside the packa...

Страница 8: ...n be used to tower install the UPS module in 2U or UPS module with one battery bank in 4U Install UPS module in 2U Assemble two feet and one short extension as one tower stand shown in step 1 Align th...

Страница 9: ...city of UPS to avoid the hazards of electric shock or fire NOTE Do not use the wall receptacle as the input power source for the UPS as its rated current is less than the UPS s maximum input current O...

Страница 10: ...tall it carefully Switch off the battery breaker before installation Warning For standard battery pack there is one DC breaker to disconnect the battery pack and the UPS But for other external battery...

Страница 11: ...h UPS is connected to an independent battery pack 5 Remove the cover of parallel share current cable port on the UPS connect each UPS one by one with the parallel cable and share current cable and the...

Страница 12: ...isplay next selection in setting menu Mute Down Button Mute the alarm Press and hold the button more than 0 5s to mute the buzzer Please refer to section 3 4 9 for details Down key Press this button t...

Страница 13: ...ltage A ampere percent centigrade degree Hz frequency AC alternating current DC direct current Indicate the output voltage output frequency load current and load percentage k kilo W watt V voltage A a...

Страница 14: ...e UPS will operate in Battery mode without interruption NOTE When the UPS is running out battery it will shut down automatically at Battery mode When the utility power is restored the UPS will auto re...

Страница 15: ...no more load to be switched off at that time you have to shut down all loads as soon as possible to protect the devices or save data Otherwise there is a risk of data loss or load failure 2 In Battery...

Страница 16: ...ble shooting table in chapter 4 for details 2 Please check the loads wiring ventilation utility battery and so on after the fault occurs Don t try to turn on the UPS again before solving the problems...

Страница 17: ...Program 15 section 3 7 in LCD setting If voltage difference remains more than 1 5V after calibration please contact your local distributor or service center for help 2 Calibrate the output voltage me...

Страница 18: ...unit 3 After it shuts down you can turn off the battery breaker for long run model and remove the parallel cable and share current cable Then remove the unit from the parallel system Second method 1...

Страница 19: ...ameter 1 There are three parameters to set up the UPS Parameter 1 It s for program alternatives Refer to below table Parameter 2 3 It s is the setting options or values for program Programs available...

Страница 20: ...ameter 2 50 0Hz The output frequency is setting for 50 0Hz 60 0Hz The output frequency is setting for 60 0Hz At If selected output frequency will be decided according to the latest normal utility freq...

Страница 21: ...range is from 51 0Hz to 54 0 Hz 60 Hz Setting range is from 61 0Hz to 64 0Hz The default value is 54 0Hz 64 0Hz 05 ECO mode enable disable Interface Setting Parameter 3 Enable or disable ECO function...

Страница 22: ...utomatic bypass is acceptable but manual bypass is not allowed Manual bypass means users manually operate UPS for Bypass mode For example pressing OFF button in AC mode to turn into Bypass mode 09 Bat...

Страница 23: ...0V to 5 7V the default value is 0V 14 Charger voltage adjustment Interface Setting Parameter 2 you may choose Add or Sub to adjust charger voltage Parameter 3 the voltage range is from 0V to 9 9V the...

Страница 24: ...2 battery numbers setting Set the battery numbers ranging from 16 20 After pressing Enter button to confirm selection then it will show charger status in Parameter 1 Parameter 3 charger status settin...

Страница 25: ...LCD display CVCF mode Description When input frequency is within 46 to 64Hz the UPS can be set at a constant output frequency 50 Hz or 60 Hz The UPS will still charge battery under this mode LCD displ...

Страница 26: ...t code Icon Bus start failure 01 None Battery SCR short circuited 21 None Bus over 02 None Inverter relay short circuited 24 None Bus under 03 None Charger short circuited 2a None Bus unbalance 04 Non...

Страница 27: ...ry second Battery unconnected Beeping every second 3 11 Warning Code Warning code Warning event Warning code Warning event 01 Battery unconnected 10 L1 IP fuse broken 07 Over charge 21 Line situations...

Страница 28: ...Remove excess loads from UPS output first Then shut down the UPS and restart it Fault code is shown as 43 The icon lights on LCD display and alarm beeps continuously UPS is overload too long and beco...

Страница 29: ...required precautionary measures may replace batteries and supervise operations Unauthorized persons must be kept well away from the batteries Verify that no voltage between the battery terminals and...

Страница 30: ...27 6 Specifications...

Страница 31: ...ing and inspection charge will apply as above 11 For hardwired products larger than 3KVA the warranty covers onsite repair for metro areas in capital cities only For equipment installed in remote loca...

Отзывы: