20
12: Hot standby function enable/disable
Interface
Setting
Parameter 2: HS.H
Enable or disable Hot standby function. You may choose following
two options in Parameter 3:
YES: Hot standby function is enabled. It means that the current
UPS is set to host of the hot standby function, and it will restart
after AC recovery even without battery connected.
NO: Hot standby function is disabled. The UPS is running at normal
mode and can’t restart without battery
13: Battery voltage adjustment
Interface
Setting
Parameter 2: Select “Add” or “Sub” function to adjust battery
voltage to real figure.
Parameter 3: the voltage range is from 0V to 5.7V, the default
value is 0V.
14: Charger voltage adjustment
Interface
Setting
Parameter 2: you may choose Add or Sub to adjust charger voltage
Parameter 3: the voltage range is from 0V to 9.9V, the default value is
0V.
NOTE:
*Before making voltage adjustment, be sure to disconnect all batteries
first to get the accurate charger voltage.
*We strongly suggest to use the default value (0). Any modification
should be suitable to battery specifications.
15: Inverter voltage adjustment
Interface
Setting
Parameter 2: you may choose Add or Sub to adjust inverter voltage
Parameter 3: the voltage range is from 0V to 6.4V, the default value
is 0V.
16: Output voltage adjustment
Interface
Setting
Parameter 2: you may choose Add or Sub to adjust Output voltage
Parameter 3: the voltage range is from 0V to 6.4V, the default value
is 0V.