background image

11 

 

3-3. Audible Alarm   

Description 

Buzzer status 

Muted 

UPS status 
Bypass mode 

Beeping once every 2 minutes 

Yes 

Battery mode 

Beeping once every 4 seconds 

Fault mode 

 

 

Beeping continuously 

Warning 
Overload   

Beeping twice every second 

Yes 

Others 

Beeping once every second 

Fault 
All 

Beeping continuously 

Yes 

3-4. Single UPS Operation 

3-4-1. Turn on the UPS with utility power supply (in AC mode)   

1)    After power supply is connected correctly, set the breaker of the battery pack at “ON” position (the 

step only available for long-run model). Then set the input breaker at “ON” position. At this time 
the fan is running and the UPS enter to power on mode for initialization, several seconds later, UPS 
operates in Bypass mode and supplies power to the loads via the bypass.     

NOTE: When UPS is in Bypass mode, the output voltage will directly power from utility after you 
switch on the input breaker. In Bypass mode, the load is not protected by UPS. To protect your 
precious devices, you should turn on the UPS. Refer to next step.   

2)    Press and hold the “ON” button for 0.5s to turn on the UPS and the buzzer will beep once.     

3)  A few seconds later, the UPS will enter to AC mode. If the utility power is abnormal, the UPS will 

operate in Battery mode without interruption. 

NOTE: When the UPS is running out battery, it will shut down automatically at Battery mode. When the 
utility power is restored, the UPS will auto restart in AC mode.   

3-4-2. Turn on the UPS without utility power supply (in Battery mode) 

1)    Make sure that the breaker of the battery pack is at “ON” position (only for long-run model).   

2)    Press the “ON” button to set up the power supply for the UPS, UPS will enter to power on mode. 

After initialization UPS will enter to No Output mode, then Press and hold the “ON” button for 0.5s 
to turn on the UPS, and the buzzer will beep once. 

3)    A few seconds later, the UPS will be turned on and enter to Battery mode. 

3-4-3. Connect devices to UPS 

After the UPS is turned on, you can connect devices to the UPS. 

1)    Turn on the UPS first and then switch on the devices one by one, the LCD panel will display total 

load level.   

2)    If it is necessary to connect the inductive loads such as a printer, the in-rush current should be 

calculated carefully to see if it meets the capacity of the UPS, because the power consumption of 
this kind of loads is too big. 

3)    If the UPS is overload, the buzzer will beep twice every second. 

4)    When the UPS is overload, please remove some loads immediately. It is recommended to have the 

total loads connected to the UPS less than 80% of its nominal power capacity to prevent overload 

Содержание Centurion RT 6000VA

Страница 1: ......

Страница 2: ...instructions in this manual strictly Save this manual properly and read carefully the following instructions before installing the unit Do not operate this unit before reading through all safety info...

Страница 3: ...INSTALLATION 6 2 5 UPS INSTALLATION FOR PARALLEL SYSTEM 8 2 5 SOFTWARE INSTALLATION 8 3 OPERATIONS 9 3 1 BUTTON OPERATION 9 3 2 LED INDICATORS AND LCD PANEL 9 3 3 AUDIBLE ALARM 11 3 4 SINGLE UPS OPERA...

Страница 4: ...nect appliances or devices which would overload the UPS e g big motor type equipment to the UPS output sockets or terminal Place cables in such a way that no one can step on or trip over them Do not b...

Страница 5: ...inals may be live when the UPS is not connected to an AC supply 1 5 Operation Do not disconnect the earth conductor cable on the UPS or the building wiring terminals in any time since this would cance...

Страница 6: ...00 4 3 Level 3 EFT IEC EN 61000 4 4 Level 4 SURGE IEC EN 61000 4 5 Level 4 CS IEC EN 61000 4 6 Level 3 Power frequency Magnetic field IEC EN 61000 4 8 Level 4 Low Frequency Signals IEC EN 61000 2 2 Wa...

Страница 7: ...y available for parallel model One share current cable only available for parallel model One battery cable option NOTE Before installation please inspect the unit Be sure that nothing inside the packa...

Страница 8: ...n be used to tower install the UPS module in 2U or UPS module with one battery bank in 4U Install UPS module in 2U Assemble two feet and one short extension as one tower stand shown in step 1 Align th...

Страница 9: ...city of UPS to avoid the hazards of electric shock or fire NOTE Do not use the wall receptacle as the input power source for the UPS as its rated current is less than the UPS s maximum input current O...

Страница 10: ...tall it carefully Switch off the battery breaker before installation Warning For standard battery pack there is one DC breaker to disconnect the battery pack and the UPS But for other external battery...

Страница 11: ...h UPS is connected to an independent battery pack 5 Remove the cover of parallel share current cable port on the UPS connect each UPS one by one with the parallel cable and share current cable and the...

Страница 12: ...isplay next selection in setting menu Mute Down Button Mute the alarm Press and hold the button more than 0 5s to mute the buzzer Please refer to section 3 4 9 for details Down key Press this button t...

Страница 13: ...ltage A ampere percent centigrade degree Hz frequency AC alternating current DC direct current Indicate the output voltage output frequency load current and load percentage k kilo W watt V voltage A a...

Страница 14: ...e UPS will operate in Battery mode without interruption NOTE When the UPS is running out battery it will shut down automatically at Battery mode When the utility power is restored the UPS will auto re...

Страница 15: ...no more load to be switched off at that time you have to shut down all loads as soon as possible to protect the devices or save data Otherwise there is a risk of data loss or load failure 2 In Battery...

Страница 16: ...ble shooting table in chapter 4 for details 2 Please check the loads wiring ventilation utility battery and so on after the fault occurs Don t try to turn on the UPS again before solving the problems...

Страница 17: ...Program 15 section 3 7 in LCD setting If voltage difference remains more than 1 5V after calibration please contact your local distributor or service center for help 2 Calibrate the output voltage me...

Страница 18: ...unit 3 After it shuts down you can turn off the battery breaker for long run model and remove the parallel cable and share current cable Then remove the unit from the parallel system Second method 1...

Страница 19: ...ameter 1 There are three parameters to set up the UPS Parameter 1 It s for program alternatives Refer to below table Parameter 2 3 It s is the setting options or values for program Programs available...

Страница 20: ...ameter 2 50 0Hz The output frequency is setting for 50 0Hz 60 0Hz The output frequency is setting for 60 0Hz At If selected output frequency will be decided according to the latest normal utility freq...

Страница 21: ...range is from 51 0Hz to 54 0 Hz 60 Hz Setting range is from 61 0Hz to 64 0Hz The default value is 54 0Hz 64 0Hz 05 ECO mode enable disable Interface Setting Parameter 3 Enable or disable ECO function...

Страница 22: ...utomatic bypass is acceptable but manual bypass is not allowed Manual bypass means users manually operate UPS for Bypass mode For example pressing OFF button in AC mode to turn into Bypass mode 09 Bat...

Страница 23: ...0V to 5 7V the default value is 0V 14 Charger voltage adjustment Interface Setting Parameter 2 you may choose Add or Sub to adjust charger voltage Parameter 3 the voltage range is from 0V to 9 9V the...

Страница 24: ...2 battery numbers setting Set the battery numbers ranging from 16 20 After pressing Enter button to confirm selection then it will show charger status in Parameter 1 Parameter 3 charger status settin...

Страница 25: ...LCD display CVCF mode Description When input frequency is within 46 to 64Hz the UPS can be set at a constant output frequency 50 Hz or 60 Hz The UPS will still charge battery under this mode LCD displ...

Страница 26: ...t code Icon Bus start failure 01 None Battery SCR short circuited 21 None Bus over 02 None Inverter relay short circuited 24 None Bus under 03 None Charger short circuited 2a None Bus unbalance 04 Non...

Страница 27: ...ry second Battery unconnected Beeping every second 3 11 Warning Code Warning code Warning event Warning code Warning event 01 Battery unconnected 10 L1 IP fuse broken 07 Over charge 21 Line situations...

Страница 28: ...Remove excess loads from UPS output first Then shut down the UPS and restart it Fault code is shown as 43 The icon lights on LCD display and alarm beeps continuously UPS is overload too long and beco...

Страница 29: ...required precautionary measures may replace batteries and supervise operations Unauthorized persons must be kept well away from the batteries Verify that no voltage between the battery terminals and...

Страница 30: ...27 6 Specifications...

Страница 31: ...ing and inspection charge will apply as above 11 For hardwired products larger than 3KVA the warranty covers onsite repair for metro areas in capital cities only For equipment installed in remote loca...

Отзывы: