Fig. 16: Optimum start and stop control
off
on
Xon
Xoff
ZSP
TRw
TRx
Start time set forward
Stop time set forward
Time switching program
Room temperature setpoint
Room temperature actual value
Reduced setp increase start
(800, 1100, 1400)
Red setp increase end
(801, 1101, 1401)
For a relatively small required heating output, the reduced room setpoint can be
raised for cold outside temperatures. The increase is dependent upon the outside
temperature. The lower the outside temperature is, the higher the reduced set-
point for the room temperature is raised. The start of the increase and the end
point can be set. Between these two points there is a linear increase of the "re-
duced setpoint" up to the "comfort setpoint".
Fig. 17: Reduced setpoint increase
TOc
TRwA1
TRwA2
TRK
TRR
TOc
Red setpoint increase start
Red setpoint increase end
Comfort nominal value
Room temperature reduced setpoint
Outside temperature composite
Programming
78