Model
Paramount three
30
40
60
80
95
115
Heating water
Adjustment range heating water temper-
atur
°C
20 - 85
Max. temp
°C
100
Operating pressure min.
bar
1,0
MPa
0,1
max.
bar
3,0
4,0
MPa
0,3
0,4
Gas-connected loads
Supply pressure for natural
gas
mbar
min. 18 - max. 25
Connected loads
Natural gas
[H
UB
9,45 kWh/m³]
m³/h 0,59-3,20 0,95-4,00 1,48-6,10 2,22-8,10 2,12-10,1
0
2,65-12,20
Supply pressure for propane
mbar
min. 42,5 - max. 57,5
Propane
[H
U
12,87 kWh/kg]
kg/h 0,44-2,33 0,70-2,95 1,09-4,51 1,63-5,98 2,33-7,38 2,72-8,94
Propane
[H
U
24,64 kWh/m³]
m³/h 0,23-1,22 0,37-1,54 0,57-2,35 0,85-3,13 1,22-3,86 1,42-4,67
Electrical power consumption
Electrical connec-
tion
V/Hz
230 V / 50 Hz
max. electr. power consumption
W
55
70
100
108
170
200
Heating mode
protective mode
W
3
3
3
3
3
3
Dimensions
Boiler weight
kg
53
53
61
72
84
84
Boiler water con-
tent
l
3,6
3,6
4,7
5.8
7,8
7,8
Height
mm
852
Width
mm
480
Depth
mm
407
407
447
542
570
570
Connections
Gas connection
3/4"
1"
Heating flow
1"
1 1/2"
Heating return
1"
1 1/2"
Technical Data Paramount Three 30-115
396532 05.11
Paramount three 30-115 kW
13
Содержание Gas condensing boiler
Страница 1: ...Installation operation and maintenance manual Gas condensing boiler Paramount three 30 115 kW ...
Страница 21: ...Fig 5 Connection plan Prior to installation 396532 05 11 Paramount three 30 115 kW 21 ...
Страница 24: ...4 8 Legend Prior to installation 24 Paramount three 30 115 kW 396532 05 11 ...
Страница 133: ...Space for notes 396532 05 11 Paramount three 30 115 kW 133 ...
Страница 134: ...Space for notes 134 Paramount three 30 115 kW 396532 05 11 ...
Страница 135: ...Space for notes 396532 05 11 Paramount three 30 115 kW 135 ...