
Function
Prog.
no.
Level
1)
Standard value
Maintenance interval
7044
E
--- months
Time since maintenance
7045
E
0 months
Fan speed ionization current
7050
E
0 rpm
Message ionization current
No |Yes
7051
E
No
Chimney-sweep function
Off | On
7130
Eu
Off
Manual control
Off | On
7140
Eu
Off
Controller stop function
Off | On
7143
E
Off
Controller stop setpoint
7145
E
Telephone customer service
7170
C
---
PStick storage pos
7250
E
0
PStick Reg data set
7251
E
PStick command
No operation | Reading from stick | Writing on stick
7252
E
No operation
PStick progress
7253
E
0 %
State PStick
No stick | Stick ready| Writing on stick | Reading from stick | EMC test
active | Writing error | Reading error| Incompatible data set | Wrong
stick type | Stick format error | Check data set | Data set disabled |
Reading disabled
7254
E
Input/output test
Relay test
No test | Everything off | Relay output QX1 | Relay output QX2 | Relay
output QX3 | Relay output QX4 | Relay output QX21 module 1 | Relay
output QX22 module 1 | Relay output QX23 module 1 | Relay output
QX21 module 2 | Relay output QX22 module 2 | Relay output QX23
module 2
7700
C
No test
Output test P1
7713
C
PWM-output P1
7714
C
Outside temperature B9
7730
C
DHW temp B3/B38
7750
C
Boiler temp B2
7760
C
Sensor temperature BX1
7820
C
Sensor temperature BX2
7821
C
Sensor temperature BX3
7822
C
Sensor temp BX21 module 1
7830
C
Sensor temp BX22 module 1
7831
C
Sensor temp BX21 module 2
7832
C
Sensor temp BX22 module 2
7833
C
Voltage signal H1
7840
C
Contact state H1
NO | NC
7841
C
Voltage signal H2 EM1
7845
C
Programming
396532 05.11
Paramount three 30-115 kW
63
Содержание Gas condensing boiler
Страница 1: ...Installation operation and maintenance manual Gas condensing boiler Paramount three 30 115 kW ...
Страница 21: ...Fig 5 Connection plan Prior to installation 396532 05 11 Paramount three 30 115 kW 21 ...
Страница 24: ...4 8 Legend Prior to installation 24 Paramount three 30 115 kW 396532 05 11 ...
Страница 133: ...Space for notes 396532 05 11 Paramount three 30 115 kW 133 ...
Страница 134: ...Space for notes 134 Paramount three 30 115 kW 396532 05 11 ...
Страница 135: ...Space for notes 396532 05 11 Paramount three 30 115 kW 135 ...